BROADCAST CONFIGURATION SUB-MENU (broAdCASt)
ITEM #
FORMAT
0
broAdCASt MEnu
1
YES/no
2
0/1/2
3
nnn
4
nnn
4.3.12 - DESCRIPTION OF THE ALARMS MENU
This menu is used to display and reset up to 5 active
alarms. It also permits alarm reset. If no alarm is active this
menu is not accessible.
ALARMS MENU
ITEM #
FORMAT
COMMENTS
0 [1]
X ALArM
X alarms are active
rESEt ALArM
Reset of alarms is requested
To reset all active alarms, continuously press
the Enter key. 'rESETALArM' is then displayed.
Press the select key again: all alarms are reset.
1 [1]
Alarm code text
Current alarm code 1**
2 [1]
Alarm code text
Current alarm code 2**
3 [1]
Alarm code text
Current alarm code 3**
4 [1]
Alarm code text
Current alarm code 4**
5 [1]
Alarm code text
Current alarm code 5**
1
This item is masked when nil
*
See section "Alarm codes"
**
Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
"time of alarm" "date of alarm" "full CCN alarm message"
- "time of alarm": xxhmm
- "date": dd-mm
- "full CCN alarm message": up to 64 characters
4.3.13 - DESCRIPTION OF THE ALARMS HISTORY MENU
ALARMS HISTORY MENU
FORMAT
ITEM #
0 [1]
Alarm code text*
1 [1]
Alarm code text*
2 [1]
Alarm code text*
3 [1]
Alarm code text*
4 [1]
Alarm code text*
5 [1]
Alarm code text*
6 [1]
Alarm code text*
7 [1]
Alarm code text*
8 [1]
Alarm code text*
9 [1]
Alarm code text*
10 [1]
Alarm code text*
....
....
19 [1]
Alarm code text*
1
This item is masked when nil
*
See section "Alarm codes"
**
Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
"time of alarm" "date of alarm" "full CCN alarm message"
- "time of alarm": xxhmm
- "date": dd-mm
- "full CCN alarm message": up to 64 characters
98
COMMENTS
When selected this item authorises a return to the main menu.
Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network. There must be only
one broadcast acknowledger in a CCN.
Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used
(see section 4.3.11.6) or if you want to configure the daylight saving time function.
This item permits activation or deactivation of the broadcast mode.
0 = the controller is not the broadcaster, and it is not useful to configure another selection in this table.
1 = broadcasts time, date, holidays and the outside temperature.
2 = for chillers only. Summertime and holidays are not taken into consideration without broadcasting the information on the bus .
OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.
OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor
connected to it.
COMMENTS
Alarm history code 1**
Alarm history code 2**
Alarm history code 3**
Alarm history code 4**
Alarm history code 5**
Alarm history code 6**
Alarm history code 7**
Alarm history code 8**
Alarm history code 9**
Alarm history code 10**
Alarm history code 10**
....
Alarm history code 20**
4.3.14 - DESCRIPTION OF THE RUNTIME MENU
4.3.14.1 - DESCRIPTION OF THE RUNTIMES 1 MENU
RUNTIMES MENU [1]
ITEM #
FORMAT
UNITS
0
RuntiME 1 menu
-
1
nnnn | M 10 | M100
hrs/10 or 100
2
nnnn | M 10 | M100
hrs/10 or 100
3 [1]
nnnn | M 10 | M100
hrs/10 or 100
4 [1]
nnnn | M 10 | M100
hrs/10 or 100
5 [1]
nnnn | M 10 | M100
hrs/10 or 100
6
nnnn | M 10 | M100
hrs/10 or 100
7
nnnn | M 10 | M100
hrs/10 or 100
8 [1]
nnnn | M 10 | M100
hrs/10 or 100
9 [1]
nnnn | M 10 | M100
hrs/10 or 100
10
- | M 10 | M100
-/10 or 100
11
- | M 10 | M100
-/10 or 100
12 [1]
- | M 10 | M100
-/10 or 100
13 [1]
- | M 10 | M100
-/10 or 100
14 [1]
- | M 10 | M100
-/10 or 100
15
- | M 10 | M100
-/10 or 100
16
- | M 10 | M100
-/10 or 100
17 [1]
- | M 10 | M100
-/10 or 100
18 [1]
- | M 10 | M100
-/10 or 100
1
This item is masked when not used
NOTES
*
Certain values are divided by 10 or by 100, so that number of hours or start-
ups of less then 10 are displayed as 0.
When the value is divided by 10 or by 100 it is displayed in turn with "M 10" or
"M100".
COMMENTS
When selected this item
authorises return to the
previous menu
Unit operating hours*
Compressor A1 operating
hours*
Compressor A2 operating
hours*
Compressor A3 operating
hours*
Compressor A4 operating
hours*
Compressor B1 operating
hours*
Compressor B2 operating
hours*
Compressor B3 operating
hours*
Compressor B4 operating
hours*
Machine starts*
Compressor A1 starts*
Compressor A2 starts*
Compressor A3 starts*
Compressor A4 starts*
Compressor B1 starts*
Compressor B2 starts*
Compressor B3 starts*
Compressor B4 starts*