PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 8)
ITEM # FORMAT
COMMENTS
0
Period X Menu
Indicates the period (X) you are going to configure.
When selected this item authorises a return to the
main menu.
1
n
n n n
Occupied period - Start time*.
1 2 3 4
00:00 to 23:59
Authorises entering the time of day at which the
occupied period starts.
2
n
Occupied period - End time*.
n n n
1 2 3 4
00:00 to 23:59
Authorises entering the time of day at which the
occupied period ends.
3
Mo- 0 or Mo- 1
1 = the period is in effect on Monday.
0 = period not in effect on Monday
4
tu- 0 or tu- 1
1 = the period is in effect on Tuesday.
0 = period not in effect on Tuesday.
5
UE-0 or UE- 1
1 = the period is in effect on Wednesday.
0 = period not in effect on Wednesday.
6
tH- 0 or tH- 1
1 = the period is in effect on Thursday.
0 = period not in effect on Thursday.
7
Fr-0 or Fr- 1
1 = the period is in effect on Friday.
0 = period not in effect on Friday.
8
SA- 0 or SA- 1
1 = the period is in effect on Saturday.
0 = period not in effect on Saturday.
9
Su- 0 or Su- 1
1 = the period is in effect on Sunday.
0 = period not in effect on Sunday.
10
Ho- 0 or Ho- 1
1 = the period is in effect on public holidays.
0 = period not in effect on public holidays.
*
n n
: hours (00 to 23). The first time the Enter button is continuously pressed,
1 2
the first two characters in the 4-digit display flash so that hours can be
adjusted.
n n
: minutes (00 to 59). Continuous pressing of the Enter key again causes
3 4
the last two characters to flash so that minutes can be adjusted.
Typical timer program:
Time
MON
TUE
WES
THU
FRI
0
P1
1
P1
2
P1
3
4
5
6
7
P2
P2
P3
P4
P4
8
P2
P2
P3
P4
P4
9
P2
P2
P3
P4
P4
10
P2
P2
P3
P4
P4
11
P2
P2
P3
P4
P4
12
P2
P2
P3
P4
P4
13
P2
P2
P3
P4
P4
14
P2
P2
P3
P4
P4
15
P2
P2
P3
P4
P4
16
P2
P2
P3
P4
P4
17
P2
P2
P3
18
P3
19
P3
20
P3
21
22
23
Starts at
P1: period 1,
0h00,
P2: period 2,
7h00,
P3: period 3,
7h00,
P4: period 4,
7h00,
P5: period 5,
7h00,
P6: period 6,
20h00,
P7: period 7,
Not used in this example
P8: period 8,
Not used in this example
SAT
SUN
HOL
P5
P5
P5
P5
P5
MON :
Monday
TUE :
Tuesday
WED :
Wednesday
THU :
Thursday
FRI :
Friday
SAT :
Saturday
SUN :
Sunday
HOL :
Public holidays
P6
Occupied
Unoccupied
Ends at
Active on
3h00,
Monday
18h00,
Monday and Tuesday
21h00,
Wednesday
17h00,
Thursday and Friday
12h00,
Saturday
21h00,
Public holidays
4.3.11.7 - DESCRIPTION OF THE HOLIDAYS SUB-MENUS
This function is used to defi ne 16 public holiday periods.
Each period is defi ned with the aid of three parameters:
the month, starting day and duration of the public holiday
period. During these public holidays the controller will
be in occupied or unoccupied mode, depending on the
programmed periods validated for public holidays.
Each of these public holiday periods can be displayed and
changed with the aid of a sub-menu.
ATTENTION: The broadcast function must be activated to
utilise the holiday schedule, even if the unit is running in
stand-alone mode (not connected to CCN). See section
4.3.11.8.
HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 16)
ITEM #
FORMAT
0
HoLidAy X Sub-menu
1
0 to 12
2
0 to 31
3
0 to 99 days
Typical programming for public holidays
A public holiday period lasting 1 day on 20th May, for instance, is configured as
follows: start month = 5, start day = 20, duration = 1
A public holiday period lasting 2 day on 25th May, for instance, is configured as
follows: start month = 5, start day = 25, duration = 2
4.3.11.8 - DESCRIPTION OF THE BROADCAST SUB-
MENU (BROADCAST)
The controller provides a broadcast confi guration menu
which you can use to confi gure the unit to be the CCN's
broadcaster, responsible for transmitting the time, outdoor
temperature, and holiday fl ags to all system elements.
This menu also authorises setting the date of the daylight
saving time. There should be only one broadcaster in a
CCN, so this table should not be confi gured if any other
system element is acting as broadcaster.
ATTENTION: If the unit operates in standalone mode (not
CCN connected) this menu can also must be used if the
holiday function is used or to correct for daylight saving
time.
COMMENTS
When selected this item authorises a return to
the configuration menu.
Start month of public holiday period
0 = period not in use
1 = January, 2 = February, etc.
Start day of public holiday period. 0 period
not in use.
Duration of the public holiday period in
days.
:
97

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aquasnap 30rsAquasnap 30rb100Aquasnap 30rb300

Tabla de contenido