COOLING UNITS
Description
Connector/channel
Evaporator pump 1 control
J2A / CH19
Evaporator pump 2 control
J2A / CH20
Evaporator heater control
J2B / CH21
Alarm relay output
J3 / CH24
Alert relay output
J3 / CH25
Operation or ready-to-start
J3 / CH26
relay output
Contact 1:
J4 / CH11
Start/stop
Contact 2:
J4 / CH12
Setpoint selection
Contact 3:
J4 / CH13
Demand limit selection 1
Contact 3 bis:
CH9
Demand limit selection 2
User safety loop input
J4 / CH15a
Contact 4:
J4 / CH14
Heat reclaim selection
Contact 5:
J12
Pump operation status
Connection to CCN
HEAT PUMP UNITS
Description
Connector/channel
Evaporator pump 1 control
J2A / CH19
Evaporator pump 2 control
J2A / CH20
Evaporator heater control
J2B / CH21
4-way valve A control
J2C/ CH22
4-way valve B control
J2C/ CH23
Alarm relay output
J3 / CH24
Alert relay output
J3 / CH25
Operation or ready-to-start
J3 / CH26
relay output
Contact 1:
J4 / CH11
Start/stop
Contact 2:
J4 / CH12
Setpoint selection
Contact 3:
J4 / CH13
Demand limit selection 1
Contact 3 bis:
CH9
Demand limit selection 2
User safety loop input
J4 / CH15a
Contact 4:
J4 / CH14
Heating/cooling selection
Contact 5:
J5C / CH18
Pump operation status
Connection to CCN
J12
78
Terminal
Board
Remarks
PD5-BASE
The control can regulate one or two evaporator pumps, and automatically
change over between the two pumps.
PD5-BASE
The control can regulate one or two evaporator pumps, and automatically
change over between the two pumps.
PD5-BASE
This (and the pipe heater for units without pumps) protects the evaporator
against frost.
PD5-BASE
Indicates alarms
PD5-BASE
Indicates alerts
PD5-BASE
Indicates if the unit is ready to start or operates.
32-33
PD5-BASE
This contact is used for unit start/stop. It is only taken into account if the
unit is under remote operation control (rEM).
65-66
PD5-BASE
This contact is only taken into account if the unit is under remote operation
control (rEM).
63-64
PD5-BASE
See the description of these contacts in sections 3.6.5 and 3.6.6.
NRCP2-BASE
This contact is only present if the energy management option is used.
34 - 35
PD5-BASE
This contact is mounted in series with the water flow control contact. It can
be used for any customer safety loop that requires that the unit is stopped,
if it is open. If it is unused this contact must be bridged.
PD5-BASE
This contact is used to select the heat reclaim mode.
PD5-BASE
If this contact is open, the pump is controlled and an alarm has tripped.
An RS-485 bus is used for connection to the CCN.
- Pin 1: signal +
- Pin 2: ground
- Pin 3: signal -
Remarks
Terminal
Board
PD5-BASE
The control can regulate one or two evaporator pumps, and automatically
change over between the two pumps.
PD5-BASE
The control can regulate one or two evaporator pumps, and automatically
change over between the two pumps.
PD5-BASE
This (and the pipe heater for units without pumps) protects the evaporator
against frost.
The control regulates the 4-way valve during heat/cool changeover or
PD5-BASE
during defrost cycles.
The control regulates the 4-way valve during heat/cool changeover or
PD5-BASE
during defrost cycles.
PD5-BASE
Indicates alarms
PD5-BASE
Indicates alerts
PD5-BASE
Indicates if the unit is ready to start or operates.
32-33
PD5-BASE
This contact is used for unit start/stop. It is only taken into account if the
unit is under remote operation control (rEM).
This contact is only taken into account if the unit is under remote operation
65-66
PD5-BASE
control (rEM).
See the description of these contacts in sections 3.6.5 and 3.6.6.
63-64
PD5-BASE
NRCP2-BASE
This contact is only present if the energy management option is used.
34 - 35
PD5-BASE
This contact is mounted in series with the water flow control contact. It can
be used for any customer safety loop that requires that the unit is stopped,
if it is open. If it is unused this contact must be bridged.
This contact is used for heating/cooling mode selection. It is only taken into
PD5-BASE
account if the unit is under remote operation control (rEM).
PD5-BASE
If this contact is open, the pump is controlled and an alarm has tripped.
PD5-BASE
An RS-485 bus is used for connection to the CCN.
- Pin 1: signal +
- Pin 2: ground
- Pin 3: signal -