Main Interface - Carrier AQUASNAP 30RB Manual De Controles Y Soluciones De Defectos

100 a 300
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The local interface enables a number of operating parameters to be displayed and modifi ed. The interface consists of
two distinct parts: the main interface (left hand section) and the summary interface (right hand section).

Main interface

It gives access to all PRO-DIALOG PLUS data and operating functions. It consists of:
A two-digit display showing the number of the item selected.
A four-digit display showing the contents of the item selected.
LEDs and buttons for unit start/stop, menu selection, menu item selection and value adjustment.
MAIN INTERFACE
BUTTON
NAME
Menu
Up arrow
Down arrow
Enter
Start/stop
MAIN INTERFACE MENU LED'S
LED
NAME
INFORMATION menu
TEMPERATURES menu
kPa
PRESSURES menu
SETPOINTS menu
INPUTS menu
OUTPUTS/TESTS menu
CONFIGURATIONS menu
ALARMS menu
ALARMS HISTORY menu
OPERATING LOG menu
80
DESCRIPTION
Permits the selection of a main menu. Each main menu is represented by an icon.The icon is lit if active.
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button aut horises
increase of the value of any parameter.
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button a u thorises
decrease of the value of any parameter.
Gives access to the modification mode, validates a modification or displays expanded item description.
Authorises start or stop of the chiller in local mode or modification of its operating type.
DESCRIPTION
Displays the general operating parameters for the unit.
Displays the unit operating temperatures.
Displays the unit operating pressures.
Displays the unit setpoints and enables them to be modified.
Displays the status of the unit digital and analogue inputs.
Displays the status of the unit outputs and enables them to be tested.
Displays the unit configuration and enables it to be modified.
Displays active alarms.
Displays the history of the alarms.
Displays the operating times and number of starts for the unit and the compressors.