Software Version; Disposal - Grundfos Conex DIS-G Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Conex DIS-G:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 56
13.2.2 Checking the relays
The first item appears in the "Test functions" menu
and does not need to be selected.
Press [OK] to change to the following items.
M1 - limit 1
OFF
M1 - limit 2
OFF
M2 - limit 1
OFF
M2 - limit 2
OFF
Alarm relay
OFF
The relays for sensor 2 can even be tested if the
device is set to "1 sensor".
When switching on a relay, the connected
Caution
warning and protection device will also be
activated!
1. For each item, press the [Up] button to switch the
corresponding relay on.
– When switched on, the relay and the
connected warning and protection device will
be activated.
– If this does not happen, check the connected
warning and protection device as well as the
cabling.
2. Press the [Up] button again to switch the
corresponding relay off.
13.2.3 Checking the current outputs
If the displayed values cannot be
Note
measured, the current output is defective.
The current output for measured value 2
Note
can even be checked if the device is set to
"1 sensor".
Checking the current outputs for measured value
1
1. Press [OK] to change to the items.
M1 - mA signal
10 mA
If the device is set to 0-20 mA.
M1 - mA signal
12 mA
If the device is set to 4-20 mA.
– Now the displayed current (10 mA or 12 mA)
should be present at the current output for
measured value 1.
2. Check this with a suitable measuring device.
3. Press the [Up] button to change to the next
current output.
M1 - mA signal
20 mA
– Now 20 mA should be present at the current
output for measured value 1.
4. Check this with a suitable measuring device.
5. Press the [Up] button to change to the next
current output.
M1 - mA signal
0 mA
If the device is set to 0-20 mA.
M1 - mA signal
4 mA
If the device is set to 4-20 mA.
– Now the displayed cur-rent (0 mA or 4 mA)
should be present at the current output for
measured value 1.
6. Check this with a suitable measuring device.
Checking the current outputs for measured value
2
1. Press [OK] to change to the following items and
check as described above.

13.2.4 Software version

1. Press [OK] to change to the item.
*Service info*
Vx.xx
dd.mm.yyyy
– Now the software version is displayed.

14. Disposal

This product or parts of it must be disposed of in an
environmentally sound way. Use appropriate waste
collection services. If this is not possible, contact the
nearest Grundfos company or service workshop.
29

Publicidad

Tabla de contenido
loading

Tabla de contenido