Table Fault diagnosis
8012138.YCB8 | SICK
Subject to change without notice
LED indicator/fault pattern /
LED indicator/fault pattern
Green LED does not light up /
Green LED does not light up
Green LED does not light up /
Green LED does not light up
Green LED does not light up /
Green LED does not light up
Yellow LED flashes; if Alarm is
present then take note of the
corresponding output signal /
Yellow LED flashes; if Alarm is
present then take note of the
corresponding output signal
Signal interruptions when ob‐
ject is detected /
Signal interruptions when ob‐
ject is detected
TABLE FAULT DIAGNOSIS
Cause /
Cause
No voltage or voltage below
the limit values /
No voltage or voltage below
the limit values
Voltage interruptions /
Voltage interruptions
Sensor is faulty /
Sensor is faulty
Sensor is still ready for opera‐
tion, but the operating conditi‐
ons are not ideal /
Sensor is still ready for opera‐
tion, but the operating conditi‐
ons are not ideal
Depolarizing property of the
object surface (e.g., tape), re‐
flection /
Depolarizing property of the
object surface (e.g., tape), re‐
flection
Measures /
Measures
Check the power supply,
check all electrical connecti‐
ons (cables and plug connecti‐
ons) /
Check the power supply,
check all electrical connecti‐
ons (cables and plug connecti‐
ons)
Ensure there is a stable power
supply without interruptions /
Ensure there is a stable power
supply without interruptions
If the power supply is OK, re‐
place the sensor /
If the power supply is OK, re‐
place the sensor
Check the operating conditi‐
ons: Fully align the beam of
light (light spot) with the re‐
flector. / Clean the optical sur‐
faces (sensor and reflector). /
Readjust the sensitivity / Re‐
flector is not suitable for the
application in question (we re‐
commend only using SICK re‐
flectors) / Check sensing ran‐
ge and adjust if necessary;
see graphic H. / Distance bet‐
ween the sensor and the re‐
flector is too long /
Check the operating conditi‐
ons: Fully align the beam of
light (light spot) with the re‐
flector. / Clean the optical sur‐
faces (sensor and reflector). /
Readjust the sensitivity / Re‐
flector is not suitable for the
application in question (we re‐
commend only using SICK re‐
flectors) / Check sensing ran‐
ge and adjust if necessary;
see graphic H. / Distance bet‐
ween the sensor and the re‐
flector is too long
Reduce sensitivity or change
the position of the sensor /
Reduce sensitivity or change
the position of the sensor