Interconnection

Direct Connection

Connect the transducer directly to the Siemens Milltronics transceiver via the two
conductor shielded cable.
When connecting to a SITRANS LUT400, a SITRANS LUC500, a MultiRanger 100/
Note:
200, or a HydroRanger 200, the white, black, and shield wires are all connected separately.
DO NOT tie the white and shield wires together.
Coaxial Connection
Connect the transducer to the Siemens Milltronics transceiver via a junction box and RG–
62 A/U coaxial cable. This setup is effective for combined runs up to 365 m (1200 ft).
When connecting to a SITRANS LUT400, a SITRANS LUC500, a MultiRanger 100/
Note:
200, or a HydroRanger 200, do NOT use coaxial cable; see diagram below for proper
procedure.
2-Wire Extension
(for SITRANS LUT400, SITRANS LUC500, MultiRanger 100/200, and
HydroRanger 200 only)
blk
Page EN-10
XPS Series Transducers – QUICK START MANUAL
blk
wht
wht
junction box
wht
drain/shield
drain/shield
extend cable using RG-62 A/U coax
extend cable using 18 AWG
shielded/twisted pair
drain/shield
A5E32282889