EN
Technical Data
Part code
Weight
Supply voltage AC
Supply frequency
Power consumption parasitic
Terminal capacity
Max load:
Incandescent lighting
Fluorescent lighting
Compact fluorescent lighting
LED lighting
Resistive heaters
Fans and ventilation equipment
Time out range
SON lighting
Max power factor correction
capacitance
Purpose
Construction
Type of action
Pollution
Software
Working temperature range
Humidity
Material (casing)
Insulation class
IP rating
Compliance
EBDSPIR-L3
0. 1 50kg
230 VAC +/- 10%
50Hz
260mW
2.5mm²
8A
6A
3A
3A
8A
3A
10s–30m
Switch loads via a
contactor
40µF
Sensing control
Independent flush
mounted, electronic
control.
Type 1.B action (micro
disconnection)
Degree 2
Class A
-10 to 35°C
5 to 95% non-
condensing
Flame retardant ABS
and PC/ABS
2
40
EMC-2014/30/EU,
LVD-2014/35/EU
DE
Technische Daten
Teile-code
Gewicht
Versorgungsspannung AC
Versorgungsfrequenz
Parasitäre stromverbrauch
Leiterkapazität
Max. Last:
Glühlampen
Neonbeleuchtung
Kompakte neonbeleuchtung
LED-beleuchtung
Widerstandsfähige heizungen
Induktiv/ventilatoren und
lüftungssysteme
Zeitüberschreitungsbereich
SON Beleuchtung
Max. Kapazität der blindleistungs-
kompensation
Zweck
Bauweise
Aktionsart
Verschmutzung
Software
Arbeitstemperaturbereich
Feuchtigkeit
Material (gehäuse)
Isolationsklasse
IP-schutzklasse
Eingehaltene normen
7
EBDSPIR-L3
0. 1 50kg
230 VAC +/- 10%
50Hz
260mW
2.5mm²
8A
6A
3A
3A
8A
3A
10s–30m
Last über schütz
schalten
40µF
Sensorsteuerung
Unabhängige
Unterputz-Elektronik
Aktion Typ 1.B
(Mikrotrennung)
Abschluss 2
Klasse A
-10 bis 35ºC
5 bis 95 % Luftfeuchtigkeit,
nicht kondensierend
Flammenhemmendes
ABS und PC/ABS
2
40
EMC-2014/30/EU,
LVD-2014/35/EU