Installation Procedure
Pipe specification
Liquid pipe
Gas
Liquid pipe
Gas pipe
pipe
1.
Pipe "A" diameter (between indoor and branch pipe depends on the indoor pipe)
Indoor (x100W)
Gas pipe
18~28
Ø9.52
32~56
Ø12.7
63~160
Ø15.88
226-300
Ø25.4
450-600
Ø28.58
Note:
If the distance between the unit and the nearest branch;:: 15m, Pipe "A" should be enlarged:
(1) If the capacity of indoor unit is 5 5.6kW, the gas pipe changes to Ø15.88 and the liquid pipe changes to Ø9.52.
(2) If 5.6kW < the capacity of indoor unit is< 16.8kW, the gas pipe changes to 019.05 and the liquid pipe changes to Ø9.52.
(3) If the capacity of indoor unit is 16.8kw, the liquid pipe changes to Ø12.7.
The first sub-manifold distance from the longest indoor unit piping length ;:: 40 meters
(1) The first sub-manifold to the nearest indoor unit main pipe (gas /liquid pipe) must increase as per the specification
(2) The distance between the nearest indoor unit distance between the indoor unit :5 40 meters\
2. Pipe "B" diameter (between the branch pipes)
Total indoor capacity after the
branch pipe (kW)
<14kW
14kW:5 X <16.8kW
16.8kW:5 X <28.0kW
28.0kW:5 X <33.5kW
33.5kW:5 X <45.0kW
45.0kW:5 X <71.0kW
71.0kW:5 X <101.0kW
101.0kW:5 X <158.0kW
158.0kW:5 X <186.0kW
186.0kW:5 X <240.0kW
240.0kW:5 X <275.0kW
>275kW
Outdoor
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
outdoor gather pipe
Liquid pipe
Ø6.35
Ø6.35
Ø9.52
Ø9.52
Ø12.7
Gas pipe
According to the pipe A diameter
Ø 15.88
Ø 19.05
Ø 22.22
Ø 28.58
Ø 28.58
Ø 31.8
Ø 38.1
Ø 41.3
Ø 44.5
Ø 50.8
Ø 54.1
the first branch pip
Note:
40VK007S-7S-QEE 40VK009S-7S-QEE gas pipe: Ø12.7,
40VK018S-7S-QEE gas pipe/ liquid pipe: Ø15.88/9.52.
Liquid pipe
Ø 9.52
Ø 9.52
Ø 9.52
Ø 12.7
Ø 15.88
Ø 19.05
Ø 19.05
Ø 19.05
Ø 22.22
Ø 25.4
Ø 25.4
14
Indoor