Installation
Safety Information
To ensure proper operation:
Installation
The eyewash portion of this fixture has been designed and 3rd party tested to meet ANSI/ISEA Z358.1. The system
must be tested periodically to be sure it is functioning properly to meet the standard. Please refer to the ANSI/ISEA
Z358.1 standard on testing requirements.
The installation, maintenance and location of all safety fixtures must comply with the requirements of ANSI/ISEA
Z358.1. Workers who may come in contact with potentially hazardous materials should be trained regarding the
location and proper operation of emergency equipment per ANSI/ISEA Z358.1.
ANSI/ISEA Z358.1 requires this unit to be used with a clean, potable, uninterrupted supply of tepid water. Bradley
plumbed emergency fixtures require a minimum of 30 psi flowing pressure in order to function as designed and meet
the ANSI/ISEA Z358.1 standard.
Before installation make sure that this equipment will meet the requirements of the potential hazardous contaminants
in your location.
Installation of this system must be completed by a qualified plumber in compliance with all national and local codes.
Compliance and conformity to drain requirements and other local codes and ordinances is the responsibility of the
installer.
Weekly Inspections
To ensure that the emergency eyewash fixture is ready to be used when needed, regular checks and maintenance
must be conducted. Weekly inspections must be conducted on all safety equipment to make sure a suitable flushing
fluid supply is present and to make sure the equipment is in good operating condition.
Water Temperature
ANSI/ISEA Z358.1 requires the eyewash to be supplied with tepid water. Suitable range is 60°F to 100°F (16°C to
38°C). Personal injury is possible outside this temperature range.
The faucet valves supplied with this fixture only controls the volume of the water supply of the faucet spout. Upon
installation, the faucet's hot water supply temperature must be checked and adjusted at its source to ensure delivery of
a safe water temperature. Water in excess of 110°F (43°C) may cause scalding.
Supplies Required
•
Piping to all water supply inlets on unit
•
Sign-mounting hardware
•
30 psi (2.0 bar) min/90 psi (6.1 bar) max flow pressure
•
125 psi (8.6 bar) max static pressure
Bradley • 215-1910 Rev. D: ECO 21-05-013
S19-500 Series & S19-505 Series
7/6/2021
3