Installation
UPS Input and Output Overview
Model Name
SUPDMB5
SUPDMB5P
SUPDMB5G
SUPDMB5HW
SUPDMB6
SUPDMB6P
SUPDMB6IEC
SUPDMB6G
SUPDMB6HW
Input
Input Line
Connection
Configuration
HW
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
L6-30P
L1, L2/N, PE(GND)
HW
L, N, PE
HW
L1, L2/N, PE(GND)
HW
L1, L2/N, PE(GND)
Building Breaker
C-Curve
Input AWG (mm
40
30
30
40
40
50
30
30
50
50
50
16
Receptacle Plate
)
Configuration
2
8 (6)
10 (4)
10 (4)
8 (6)
8 (6)
None
6 (10)
10 (4)
10 (4)
6 (10)
6 (10)
6 (10)
None