Important Safety Instructions

SAVE THESE INSTRUCTIONS
This manual contains important instructions and warnings that should be followed during the installation, operation, maintenance and
storage of all Tripp Lite UPS Systems, Batteries and Detachable PDM. Failure to heed these warnings may affect your warranty.

Explanation of Symbols

Caution—risk of danger
Hot—overheating may occur
Electrical shock hazard
Protective earth ground
Bonding ground
Recyclable—contains lead

UPS Location Warnings

• Your UPS/PDM is intended to be used in a temperature-regulated, indoor area that is relatively free of conductive contaminants. Install
your UPS/PDM indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight.
• Ambient room temperature should be between 32°F and 104°F (0°C and 40°C).
• Leave adequate space around all sides of the UPS for proper ventilation.
• The PDM provides the convenience of multiple outlets, but DOES NOT provide surge or line noise protection for connected equipment,
when in Bypass Mode.
• Do not mount unit with its front or rear panel blocked. Mounting in this manner will seriously inhibit the unit's internal cooling, eventually
causing product damage not covered under warranty.
UPS Installation and Connection Warnings
All Models
CAUTION: Installation should be performed by qualified professional electrical service personnel only.
• Install in accordance with National Electrical Code standards. Be sure to use the proper overcurrent protection for the installation in
accordance with the plug/equipment rating.
• Be sure to use an upstream circuit breaker with a C curve.
• Overcurrent protection shall be provided in the end-use application, installed in accordance with local and national electrical wiring
regulations.
• Short-circuit backup protection and overcurrent protection is provided by the building Installation, in the hardwire configuration (Bypass
and Economy Modes).
• Install at a height not exceeding 1 m (3.3 ft.).
• Equipment is intended for use on a TN-S power distribution system.
Select Models Come Equipped with an L6-30P Plug
CAUTION: To reduce the risk of fire, connect only to a circuit provided with 30A maximum branch circuit overcurrent protection in
accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
• The AC mains L6-30P plug serves as the disconnect device. The electrical outlets supplying power to the equipment must be installed
near the equipment and easily accessible. Alternatively, a local disconnect may be provided.
• DO NOT use the hardwire AC supply input option when an L6-30P plug is present. Doing so may cause a catastrophic dangerous situation.
• When the hardwire AC output is used, appropriate output overcurrent protection must be provided.