10. DISPLAY. There are 2 possible displays in normal operation that can be switched by pushing
Hz
Bar
40
2,5
Hz: Instantaneous rot. frequency main pump.
Bar: Instantaneous pressure.
Pset: Target pressure.
11. START UP
§ Be sure that the pump is correctly primed
§ Connect the device to the electric supply with the magnetothermic switch, FAILURE led light will be ON. Wait
for 10 seconds while the device is doing the autotest. Once it finishes, led light FAILURE is OFF and led light
LINE is ON. The LCD screen will show message "SPEEDBOX DUO SET " and inmediately the language display
of the configuration mode.
§ The device is ready for being configured.
12. ADVANCED MENU. Special configuration, there is no need to adjust these values, they are factory set.
Using pq we can change the values and press
configuration sequence press MENU. After every ENTER it will appears automatically the different screens that
constitute the configuration sequence.
ADVANCED
MENU
MAX. FREQUENCY
50.0 Hz
PRESSOST. MODE
ON
START P THRESH
2.5 bar
START DELAY
1 s
STOP THRESH
3.5 bar
STOP DELAY
1 s
PROPORTIONAL
20
ACCELERATION
10
DECELERATION
10
DEFAULT PARAM.
NO
RESET REGISTERS
NO
UNITS
bar
Pset
p
2,6
To start the configuration secuence press MENU + ENTER during 3"
By mean of keys pq it can be adjusted the maximum working frequency.
In case of failure of the inverter, the system can operate in pressure
dependent mode. Enabling this option, you will be able to set the start and
stop pressure (following steps). [ON/OFF]
In PRESSURE DEPENDENT MODE (inverter failure), by mean of ▲▼ is
adjusted the start pressure. Press ENTER for validation. [0-12 bar]
By mean of ▲▼ is adjusted the time delay on the start. Press ENTER for
validation. [1-999 seconds]
In PRESSURE DEPENDENT MODE (inverter failure), by mean of ▲▼ is
adjusted the stop pressure.
[0-12 bar]
By mean of ▲▼ is adjusted the time delay on the stop. Press ENTER for
validation. [1-999 seconds].
PI parameter, factory set. For any doubt contact with the manufacturer.
Using pq it can be adjusted the acceleration. Rank 5-20 (Hz/s). Press
ENTER to confirm.
Using pq it can be adjusted the desaceleration. Rank 5-20 (Hz/s). Press
ENTER to confirm.
Restore factory default settings.
Reset the registers of functions and allarms.
Pressure units. [bar/psi]
INV
REL
TMP Bar
6.8
8.2
50
INV: Instantaneous current drawn by inverter pump (Amps).
REL: Instantaneous current drawn by relay pump (Amps)
TMP: Electronics temperature.
Bar: Instantaneous pressure.
ENTER for validation. Whenever we want to quit the
2.5
p
.
12