3. MAIN CHARACTERISTICS
1 frequency inverter for the pumps control.
n
1 power relay to alternate the main pump.
n
Wall-mounted
n
Control and safety system against overload.
n
Control and safety system against dry run.
n
ART function (Automatic Reset Test). If the device has been stopped due to the action of the safety system
n
against over-current, the
supply could have been restored
Automatic restore system after an interruption of power supply. System is activated in AUTOMATIC mode
n
keeping the configuration parameters (see "CONFIGURATION" chapter).
STC function (Smart Temperature Control ). Overheating protection. This device has protection to avoid
n
overheating failures that could be produced in adverse environmental conditions, operating continuously and
with current draw close to the nominal power of the device. If the electronics exceed 85ºC under these
conditions, the maximum operating frequency will automatically dicrease in order to reduce consumption. As
soon as the temperature of the electronics drops to 80ºC, normal operation will be restored.
External pressure transducer (4.20 mA) under demand.
n
External programable input with three options: Level, ON/OFF and Second pressure.
n
Control panel (Fig.1):
n
LCD screen, for alarm menu with permanent pressure indication.
n
START/STOP push-buttons to act by hand each one of the pumps
n
ENTER pushbutton to save data in memory.
n
ON/OFF
pushbutton to
n
MENU push-button
n
Keyboard for the access to programming menu.
n
Digital gauge.
n
Register of operational controls: infomation about operating hours, counter of starts, counter of connections to
n
the power supply.
Register of alarms: information about type and number of alarms since the starting up of the device.
n
4. CLASSIFICATION AND TYPE
According to EN: 60730-1 and EN:60730-2-6 this unit is a control electronic device for pressure groups, with
flexible cable for permanent assembly type Y, action type 1Y (transistor output). Operating value: flow 2.5
l/min. Degree of contamination 2 (clean environment). Software Class A.
Impulse rating voltage: cat II / 2500V. Applied temperature for the ball pressure test: enclosure (75ºC) and
PCB (125ºC). Control circuit for AC motor cos fi
According to EN 61800-3 this device is C2 class.
5. TECHNICAL CHARACTERISTICS
TYPE
Power suply voltage
Frecuency
Output
Nominal. current
Max. peak of current.
Range of set pressure
Protection degree
Max. enviorn. temp.
Relative humidity
Cooling method
Net weight
ART
tries to connect the pump, with a programmed periodicity because the water
change rom AUTOMATIC to MANUAL mode or vice versa.
≥
0,5 - 16 bar or 0.5 - 10 bar or 0 - 25 bar (type config.)
0,75 (3-phase).
~3x400 Vca +10% -20%
Maximum relative humidity 80% for temperatures up to 31 °C,
decreasing linearly to 50% relative humidity at 40 °C
Forced convection
DUO SET
50/60 Hz
~3x400 Vca
9A
20% 10 sec.
IP 65
5 - 40 ºC
4,6 kg
9