Franklin Electric MONODRIVE UTILITY Manual Del Usuario página 17

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Risk of damage to VFD
Follow all wire routing and grounding instructions carefully. Inductive currents caused by paral-
lel wiring, or close proximity between high voltage and control wiring can cause unexpected
behaviors.
Do not run input power and motor wires in the same conduit.
Do not run motor wires from multiple VFDs in common conduit.
Do not run control wiring parallel with high voltage wiring.
Do not install a magnetic contactor or disconnect in the motor circuit.
Do not run VFD wiring parallel with house or out-building wiring.
Do not use aluminum wires for VFD connections.
Do not use with a Ground Fault Circuit Interrupter (GFCI) between breaker panel and motor.
All wiring must comply with the National Electrical Code and local codes.
Improper splicing or damage to motor cable insulation may expose the conductor(s) to
moisture and can produce motor cable failure.
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional
local codes, or the equivalent. Drive shall be protected by fuse or inverse-time circuit breaker only,
rated 300 V, and a maximum 300% of full load motor output current rating as noted below.
Fuse/Circuit Breaker and Wire Sizing
Model
Input
Voltage
230
230
MonoDrive
230
Utility
230
230
1
Based on a 3% voltage drop.
90 C Insulation only.
*
Note: MonoDrive Utility minimum breaker amps may be lower than AIM Manual specifications
because of the soft-starting characteristic of the drive.
Maximum Motor Cable Length
Model
Motor Family
214 505 xxxx
214 507 xxxx
MonoDrive
214 508 xxxx
Utility
224 300 xxxx
224 301 xxxx
1
Based on a 5% voltage drop with 1000 ft limit.
,
or malfunction can occur.
Motor HP
Fuse/
Breaker
Amps
14
1/2 (0.37 kW)
15
130
3/4 (0.55 kW)
15
130
1.0 (0.75 kW)
20
70
1.5 (1.1 kW)
25
2.0 (1.5 kW)
25
Motor
Horsepower
Voltage
230
1/2 (0.37 kW)
230
3/4 (0.55 kW)
230
1.0 (0.75 kW)
230
1.5 (1.1 kW)
230
2.0 (1.5 kW)
AWG Copper Wire Sizes, 75° C Insulation, and
Panel to Drive Cable Lengths (in feet)
12
10
8
205
340
525
150
250
390
*
*
185
285
110
140
215
105
167
AWG 600V Copper Wire Sizes, 75° C Insulation, and
Motor Cable Lengths (in feet)
14
12
400
650
300
480
250
400
190
310
150
250
INSTALLATION AND SETUP
Electrical Installation
1
6
4
3
2
835
1315
1635
2150
620
975
1210
1595
450
715
885
1165
340
540
670
880
264
421
530
669
1
10
8
6
1000
760
1000
630
990
480
770
1000
390
620
970
1
1/0
2720
2020
1475
1115
843
1062
4
17

Publicidad

Tabla de contenido
loading

Tabla de contenido