Firmware Updates
Firmware Version Readout
The MonoDrive Utility is able to use the display LEDs to perform a flash sequence to indicate the
version of firmware currently installed on the drive in XYZ format. Follow this procedure to identify
the firmware version:
1. Remove power from the drive and allow 5 minutes for internal voltage to dissipate.
2. Remove the drive cover.
3. Place DIP SW2 – Position 8 in the ON (up) position.
4. Reinstall the drive cover before applying power to the drive.
5. Apply power to the drive. The firmware readout procedure will begin automatically as follows:
• All three (3) LEDs will rapidly flash together to indicate that the readout procedure is start-
ing.
• The Power LED (top/green) will slowly flash at a rate of 1 flash/second. The number of
flashes indicates the X value of the drive firmware version.
• The Running LED (middle/green) will slowly flash at a rate of 1 flash/second. The number of
flashes indicates the Y value of the drive firmware version.
• The Fault LED (bottom/red) will slowly flash at a rate of 1 flash/second. The number of
flashes indicates the Z value of the drive firmware version.
• These steps will repeat indefinitely.
6. Remove power from the drive and allow 5 minutes for internal voltage to dissipate.
7. Remove the drive cover.
8. Place DIP SW2 – Position 8 in the OFF (down) position.
9. Reinstall the drive cover.
10. Power on the drive. The drive will return to normal operation.
MAINTENANCE
Firmware Updates
35