6
COMMISSIONING THE UNIT AND THE INSTALLATION
6.1
Filling and air purge of unit and installation
6.1.1
CH system
1.
Insert the unit's plug into a socket.
The unit may carry out a self-check:
The unit will then go into the off setting:
pressure is shown on the temperature display.
In case of a CH pressure lower than 0.5 bar, the CH
pressure will be displayed flashing on the display.
In the off setting, the CH pressure will be displayed.
2.
Connect the filling hose to the fill/drain tap and fill the installation with clean drinking
water, up to a pressure between 1 and 2 bar if the installation is cold (to be read
from the temperature display).
3.
Aerate the system with the manual aerator (A).
Upon request, an automatic aerator can be fitted onto the unit instead of the manual
aerator.
4.
Aerate the installation with the manual aerators on the radiators.
5.
Top up the CH installation if the pressure has dipped too low due to the aeration.
6.
Check all couplings for leaks.
7.
Check whether the siphon is filled with water.
WARNING
If the siphon is not filled with water, combustion gases
may be released into the room.
WARNING
If an additive is added to the CH water, it must be
suitable for the materials used in the unit, such as
copper, brass, stainless steel, steel, plastic and rubber.
The additive should preferably have a KIWA/ATA/Atest
certification.
6.1.2
DHW supply (only applicable in indirectly fired tank)
1.
Open the main tap to bring the warm water section up to pressure.
2.
Aerate the tank and the pipe system by opening a warm water tap. Leave the tap
open until all air has flowed out of the system.
3.
Check all couplings for leaks.
6.1.3
Gas supply
1.
Aerate the gas pipe with the initial pressure measuring nipple (D) on the gas block.
2.
Check all couplings for leaks.
3.
Check the initial pressure and offset pressure (see par. 7.7).
2
(on service display).
-
(on service display) and the CH
34