Use this setting when scanning a surface and looking specifically for bars that are located within a certain
depth. For example, if checking for 40 mm minimum depth of cover, set the value to 40 mm (1.57") (for quality
assurance measurements add an extra 2 mm (0.08") to account for any accuracy limitations). A signal tone
is emitted and the LED lights only if a reinforcing bar located within 40 mm (1.57") of the surface is detected.
Use the arrow buttons to select the minimum depth
function and then press Confirm.
Minimum depth function disabled
When the value is set to "0", the function is deactivated
and appears as above. Use the arrow buttons to enter
the desired depth value and then confirm the setting by
pressing the Confirm button. The system returns to the
main menu.
Note
If reinforcing bars are located at depths greater than the minimum depth set, no signal tone is emitted
and no LED lights.
Scan direction
This setting is used to set the direction in which Quickscan recording is performed. Although they have no
direct effect on any measurement values later obtained from the tablet or PC application, the settings help to
ensure that individual Quickscan recordings are subsequently correctly displayed in Hilti PROFIS Ferroscan
MAP (data evaluation and presentation application) and that the depth values correspond with the actual
surface of the structure. This makes it easier to subsequently locate the positions of areas with inadequate
cover. The scanning direction is saved together with each scan.
Select the desired scanning direction and press the
Confirm button.
Bar diameter
This setting must be made in order to obtain an accurate depth-of-cover measurement (= rebar depth).
Depth can be measured accurately only when correct rebar diameter has been entered.
Use the arrow buttons to select the bar diameter function and then press the Confirm button.