The following table shows the electrical connections in Fig. 1:
Terminals
SEL 115/230
L/N/GND
MOT
COM/SWO/SWC
ANT/SHIELD
COM
S.S.
STOP
PHOT
BLINK
+ 24V -
AUX
J6
M6
The radio receiver in this product is compatible only with ARC (Advanced Rolling Code) transmitters which, thanks to 128 bit coding,
guarantee superior anti-copying security.
CAUTION! THE AUTOSET PROCEDURE DESCRIBED BELOW IS MANDATORY!
During the AUTOSET phase, the control unit performs a number of opening and closing movements during which essential operating parameters are
set, including:
- Start- and end-of-run positions.
- Start of the slowing phases.
- Torque values applied during panel movement.
- Recognition of the device connected to the PHOT input.
Procedure:
1) Position the leaf in th e CLOSURE position (check activation of the SWC limit switch)
2) With the control unit connected to the mains, press and hold down the PU1 + PU2 keys until the 3 red LEDs light up cyclically.
3) The AUTOSET procedure starts, some opening and closing movements are commanded.
4) At the end of the procedure the panel stops in the open position and the LED lights remain steady for 5s to confirm AUTOSET
correctly carried out.
CONTROL UNIT CP.B24-SW
ELECTRICAL CONNECTIONS
Function
Mains power supply selection
Power supply
Motor
Adjustable
Antenna
General
Step-by-Step
STOP
Photocell
Flashing
24 Vac/dc
Auxiliaries output
X.BE
Battery charger
ARC TRANSMITTERS
IMPORTANT, PLEASE READ CAREFULLY:
Description
230 Vac 50/60 Hz (from 207 to 253 Vac) jumper M7 OPEN
115 Vac 50/60 Hz (from 102 to 125 Vac) jumper M7 CLOSED
Mains power supply input 115Vac/230Vac selectable via M7 jumper
Quick connector for the connection of 24 Vdc motor
Quick connector for the connection of the limit switches
COM: Common - SWO Limit Switch Opens (N.C. contact) - SWC Limit switch closes
(N.C. contact)
Built-in radio receiver antenna connection
ANT: Signal / SHIELD: Display
Common for all control inputs.
Step-by-step key input (N.O. contact).
The control unit executes a command at each S.S. impulse according to the se-
quence:
OPENS>STOP>CLOSES>STOP>OPENS or OPENS>CLOSES>OPENS.
See dip switch 2
STOP key input (N.C. contact)
Settable as a PED key (N.O. contact) see dip switch 2
Photocell input (N.C. contact) active in the closure and opening phase according to
the setting of dip switch 2
24Vdc flashing connection 15W max.
Power supply output accessories 24Vdc/500mA max.
Clean contact (N.O.) configurable using Dip Switch 1 as SCA (gate open indicator
light) or second radio channel.
Quick connector for KNX interface card (item X.BE - See paragraph KNX)
Quick connector for optional battery charger card connection.
AUTOSET