Commissioning - SICK WSE16 Serie Instrucciones De Uso

Ocultar thumbs Ver también para WSE16 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 63
6

Commissioning

8020353 | SICK
Subject to change without notice
Health
Health output: The sensor (WEO16P, WEO16I) features a pre-failure notification output
("Health" in connection diagram
ready for operation to a limited extent or the cable has been interrupted. Possible
causes: Sensor or reflector is contaminated, sensor is out of alignment, cable is dam‐
aged. In the good state: HIGH (1), if excessively contaminated or in the event of cable
interruption LOW (0). The yellow LED indicator flashes in this case.
Table 5: Alarm / Health
Test input
Test input: The sensors (WSO16P, WSO16I) feature a test input ("Test" in
which can be used to switch the sender off and, therefore, check that the sensor is
functioning correctly: If female cable connectors with LED indicators are used, you must
ensure that Test is assigned accordingly.
There must be no object between the sender and receiver; activate the test input (see
the connection diagram
table
tion of an object is simulated. Refer to
switching output fails to behave in accordance with
ditions. See section Troubleshooting.
Table 6: Test
Alignment
ELECTRICAL INSTALLATION
table
5, which issues a notification if the sensor is only
Alarm (≤ 100 mA)
+ (L+)
Alarm
‒ (M)
+ (L+)
Alarm
‒ (M)
6, Test at 0 V). The send LED is shut down or the detec‐
table
4,
table 6
to check the function. If the
table
Health (≤100 mA)
+ (L+)
Health
‒ (M)
+ (L+)
Health
‒ (M)
table
6),
4, check the application con‐
Test
+ (L+)
Test
‒ (M)
+ (L+)
Test
‒ (M)
5
9

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wse16pWse16i

Tabla de contenido