Descargar Imprimir esta página

Suspending The Unit; Installing The Condensate Pipe - Baxi RZGNK35 Manual De Instalación Y Mantenimiento

Ocultar thumbs Ver también para RZGNK35:

Publicidad

Idiomas disponibles

Idiomas disponibles

en
5 Installation
Fig.187
Rear side air inlet
5.8.2

Suspending the unit

5.8.3

Installing the condensate pipe

Fig.188
1~1.5 m
162
MW-6020087-1
Important
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
Ensure the condensate can properly be drained. Install the unit
slightly sloped towards the drain tap.
1. Mount the fasteners of the indoor unit in one of the following ways:
with a dowel on which the suspension bolt is screwed.
with a suspension rod fixed directly on the hard structure (steel or
wood).
MW6020094-01
2. Install a nut to the end and a spring washer to the suspension bolt.
3. Install the indoor unit to the suspension bolt then a washer and a nut
to secure.
4. Adjust the relative position of the suspension hook on the suspension
bolt so that the unit can be in level position in all directions.
5. Tighten the nut and ensure that four hooks are in close contact with
the nuts and washers, to fix the indoor unit.
6. Install the locknut and screw it down to secure the installation.
7. Ensure the unit is secure and does not shake or sway. Ensure that the
center of the indoor unit is aligned with the installation.
MW6020097-01
1. Connect the condensate pipe to the drain tap.
2. Ensure there is a downward gradient of 1/100-150. The pipe should
not rise at any point.
3. Insulate the condensate pipe and drain tap to prevent condensation.
4. Start the air conditioner.
5. Pour water directly into the condensate pan.
6. Check that the water is drained off smoothly and correctly.
>1/100
MW-6020089-1
7798731 - v01 - 18112021

Publicidad