Descargar Imprimir esta página

Recommended Cable Cross Section - Baxi RZGNK35 Manual De Instalación Y Mantenimiento

Ocultar thumbs Ver también para RZGNK35:

Publicidad

Idiomas disponibles

Idiomas disponibles

5.11.2

Recommended cable cross section

Tab.105
Appliance
RZGT35
RZGT50
RZGT70
RZGT100
RZGT120
RZGT140
RZGT160
7798731 - v01 - 18112021
Power supply
Power cable
type
2
(mm
)
Single phase
3 x 2.5
Single phase
3 x 2.5
Single phase
3 x 2.5
Single phase
3 x 4.0
Single phase
3 x 4.0
Three phase
5 x 2.5
Three phase
5 x 2.5
Important
Electrical conformity for earthing
France
Belgium
Germany
Other countries
Important
The installation must be fitted with a main switch.
Caution
Power the appliance via circuits that include omni-polar switches
with contact opening distance of 3 mm or more.
Single phase models: 230 V (+6%/-10%) 50 Hz
The installer must provide the power supply cables and connect them.
Caution
Secure the cables with the cable ties supplied. Be careful that you
do not invert any of the wires.
The electrical characteristics of the mains power supply available must
correspond to the values given on the data plate.
The cable will be carefully chosen according to the following information :
Maximum intensity of the outdoor unit. See table below.
Distance of the appliance from the original power supply
Upstream protection.
Neutral operating conditions.
Important
The maximum permissible current on the power supply cable of
the indoor unit must not exceed 6 A.
Power cable to in­
2
door unit (mm
)
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
3 x 1.5
Important
For the "inverter" outdoor unit power supply, use a residual-
current device (RCD) compatible with high harmonics:
a type A residual-current device may be sufficient for single-
phase applications,
if not, a type B or equivalent residual-current device may be
sufficient for three-phase and single-phase applications.
NFC 15–100 standard
RGEI standard
VDE 0100 standard
Installation standards in force
Communication ca­
Circuit
breaker
2
ble (mm
)
curve C
(A)
2 x 0.75
16
2 x 0.75
16
2 x 0.75
16
2 x 0.75
25
2 x 0.75
25
2 x 0.75
32
2 x 0.75
32
en
5 Installation
Maximum
amperage
(A)
11
12
16
23.5
24.9
27
27
171

Publicidad

loading