Descargar Imprimir esta página

Flaring Work; Connecting The Refrigerant Connections To The Indoor Unit; Connecting The Refrigerant Connections To The Outdoor Unit - Baxi RZGNK35 Manual De Instalación Y Mantenimiento

Ocultar thumbs Ver también para RZGNK35:

Publicidad

Idiomas disponibles

Idiomas disponibles

5.10.2

Flaring work

Fig.195
a
b
d
c
c
5.10.3

Connecting the refrigerant connections to the indoor unit

Fig.196
Fig.197
Pipe adapter
MW-6070061-01
5.10.4

Connecting the refrigerant connections to the outdoor unit

Fig.198
7798731 - v01 - 18112021
g
e
f
h
MW-1002117-1
MW-1001648-1
Carry out flaring work using a flaring tool and compare the flared work with
the provided figure. If the flare is noted to be defective, cut off the flared
section and do flaring work again.
Good example:
a Smooth all around
b Inside is shining without any scratches
c Even length all around
Bad examples:
d Too much
e Titled
f Scratch on flared plane
g Cracked
h Uneven
Caution
Use a counter-key to prevent the refrigeration link from twisting.
1. Cut the refrigerant pipes coming from the outdoor unit with a pipe
cutter and deburr.
2. Unscrew the protective cap from the liquid line of the refrigerant
connector and discard.
3. Check the exchanger leak-tightness. Push a screwdriver gently into
the 1/4" nut. A release noise should be heard, which is proof that the
exchanger is leak-tight.
4. Remove the liquid line nut and throw it away.
5. Remove the gas nut and throw it away.
6. Add a pipe adapter if necessary
7. Engage the nuts from the accessory bag onto the refrigerant pipes.
8. Flare the refrigerant connections.
9. Apply refrigerant oil to the flared parts to facilitate tightening and
improve the seal.
10. Tighten the connections, observing the given tightening torques.
Tab.102
External diameter of
the pipe (mm/inch)
6.35 - 1/4
9.52 - 3/8
12.7 - 1/2
15.88 - 5/8
19.05 - 3/4
Caution
Use a counter-key to prevent the refrigeration link from twisting.
1. Remove the protective side panel from the outdoor unit.
2. Check that the stop valves are closed.
3. Remove the protective caps from the valves and throw them away.
External diameter of
Torque load (N.m)
the cone fitting (mm)
17
14 - 18
22
34 - 42
26
49 - 61
29
69 - 82
36
100 - 120
en
5 Installation
167

Publicidad

loading