Anomalies related to the plumbing circuit
PROBLEM
The thermostove boils
under "modulation"
that reaches the
temperature set on
the thermostat of the
thermostove
The thermostove goes
into "modulation"
as it reaches the
temperature set on
the thermostat of the
thermostove even
at low temperatures
of the water in the
thermostove
High variability of
domestic hot water
temperature (where
existing)
Exits little hot water
(where existing)
Never turn off the heater by removing electricity. Let always complete the
shutdown cycle, otherwise you may damage the structure and have trouble
lighting in the future.
50
POSSIBLE CAUSE
1. It 'been set to a value of
thermostat too high
2. It was set too much power to
the implant.
1. Modify the parameter for the
maximum smoke temperature
modulation to edit
2. Dirty thermostove: the fumes
are too high temperature.
1. Water flow is too high
1. Insufficient water pressure in
the network
2. Tap or mixer clogged with
limescale
3. Water group clogged
4. The heat exchanger does not
work
5. Air in: pump cavitation for the
presence of air, the water does not
rotate.
REMEDY
1. Lower the temperature in the thermostove
2. Reduce the value of operating power
1. Contact your Authorized Assistance Center
2. Clean the tube bundle
1. Reduce the flow of water (4/6 liters per minute)
1. Check the setting of the pressure reducing valve
2. Install a water demineralizer
3. Check and clean the sanitary kit
4. Replace the plate heat exchanger
5. Bleed the brake system, remove air by venting
the radiators.