2. Selecting the installation location
/2.2. Minimum installation area
If you unavoidably install a unit in a space where all four sides are blocked or there are depressions, confirm that one of these situations (A, B or C) is satisfied.
Note: These countermeasures are for keeping safety not for specification guarantee.
A) Secure sufficient installation space (minimum installation area Amin).
Install in a space with an installation area of Amin or more, corresponding to refrigerant quantity M (factory-charged refrigerant + locally added refrigerant).
M [kg]
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
B) Install in a space with a depression height of [ 0.125 [m].
Height from the bottom of
0.125 [m] or less
C) Create an appropriate ventilation open area.
Make sure that the width of the open area is 0.9 [m] or more and the height of the open area is 0.15 [m] or more.
However, the height from the bottom of the installation space to the bottom edge of the open area should be 0.125 [m] or less.
Open area should be 75% or more opening.
75% or more opening
Note: About the indoor unit, there are no installation restrictions due to the use of R32 refrigerant.
Please refer to the indoor unit installation manual and check the required installation area.
Amin [m²]
12
17
23
28
34
39
45
50
56
62
67
73
78
84
Width W 0.9 [m] or more
Amin
Height from the bottom of
0.125 [m] or less
Height H 0.15 [m] or more
Height from the bottom
0.125 [m] or less