4.3
Mounting steps
x
How to connect the filter:
1. Loosen the four screws 0 and remove the terminal cover 1.
2. Connect the filter input cable to terminals 1U1, 1V1, 1W1.
Connect the filter output cable to terminals 1U2, 1V2, 1W2.
–
Use shielded cables.
–
Connect the two PE conductors to the PE stud using ring cable lugs
(PE connection must comply with EN 50178).
–
Observe tightening torques.
3. Turn down the shield and connect it to the shield sheet (PES) with a surface
as large as possible.
Fix the shield with a metal cable tie or hose clip 2.
–
Use an additional cable tie for strain relief 3.
–
4. Insert the terminal cover 1 and fix it with four screws 0.
EDKZS3Y200 DE/EN/FR/ES/IT 1.1
All manuals and user guides at all-guides.com
Stripping length depends on the filter size
Electrical installation
SSP94SF107
l
Mounting steps
xxxx
U
V
W
1U1
1V1
1W1
EZS3-xxxA200
1U2
1V2
1W2
M
3~
SSP94SF004
SSP94SF109
4
19