Descargar Imprimir esta página

Sime FORMAT DGT 25/15 BF Manual De Instrucciones página 82

Publicidad

Idiomas disponibles

Idiomas disponibles

– MODULATOR ANOMALY "ALARM 11"
The modulator is not connected.
When during functioning the boiler
detects zero current to the modulator,
the display will show anomaly "AL 11".
The boiler will function at minimum
power and the anomaly will be de-acti-
vated when the modulator is reconnec-
ted or when the burner stops working.
– CONFIGURATION ANOMALY "ALARM
12"
Anomaly in the SEALED/OPEN configu-
ration. There may be a conflict between
the values set by the installer for PAR 1
and the self-detection carried out by the
card causes the activation of the alarm:
the boiler will not function and the display
will show anomaly "AL 12".
Reset PAR 1 to de-activate the alarm or
check the pressure switch/combustion
product thermostat and relative connec-
tion.
– HEATING PROBE POSITIONING ANO-
MALY SM1/SM2 "ALARM 16" (fig.
24/d)
If the probe does not detect a tempera-
ture increase after burner ignition, the
burner switches off after 10 seconds,
the display shows anomaly AL 16 eand
the4 green LED stays on.
If the anomaly occurs three times within
24h lthe boiler blocks, the display conti-
nues to show anomaly AL 16 and the red
LED switches on.
Press (
) on the control panel to re-start
the boiler.
– SENSOR
ALIGNMENT ANOMALY
"ALARM 17"
When the two sensitive elements of the
heating probe (SM1/SM2) dif fer to
each other by more than 16°C the boiler
does not function and the display shows
anomaly AL 17.
Reaplace
t he
heating
(SM1/SM2) to restore functioning.
82
Fig. 24/d
pr obe

Publicidad

loading