NOTE: Automatic "By-pass" operation is deactivated when:
- The Outdoor Air Temperature is lower than 15°C.
- The "No Frost" function is active.
- Following activation or deactivation of the by-pass, the device maintains the by-pass status "on" or "off" for 60 minutes,
unless the user intervenes.
- The by-pass function is not called up in the event of a fault in the temperature sensors.
• "Post-ventilation" Function
This kind of function is automatically activate after:
- every time Pre-Heater is turned off (if Pre-Heater installed)
- every time you turn the Appliance off (OFF: available only via APP) indoor air is extracted at the max speed (about 2
This system behavior is normal and should not be considered as an anomaly.
• "Holiday" functioning
Special mode of operation: manually enabled and useful if the user leaves the room for a longer period of time.
Operation (indicated by active LED 1) includes:
- fixed "30% less of Minimum " speed (no other speeds, no OFF equipment);
When the mode is active, the message "Holiday" appears on the display: see "Home Page" in the "Panel functions".
NOTE: By activating the mode "Holiday" other product functionings/selections will be deactivated.
To re-activate other product functionings/selections, need to deactivate the Mode "Holiday" before.
both motor-fans active (about 3 minutes) to avoid
over heating.
minutes) to avoid condensate presence on the heat
exchanger.