"Speed Adjustment Menu" page
Select "Speed" from the Installer "Use menu" to access the speed adjustment menu.
SPEED
VSUP1
VEXH1
VSUP2
VEXH2
VSUP3
VEXH3
VSUPB
VEXHB
Motor speed can be adjusted depending on the system flow rates, selecting:
VSUP1 = Clean air outlet inside the room (minimum speed '1')
VSUP2 = Clean air outlet inside the room (speed '2')
VSUP3 = Clean air outlet inside the room (speed '3')
VSUPB = Clean air outlet inside the room (maximum speed - 'Boost')
Clean air outlet inside the room: see A fig. 2 / Stale air outlet to outside: see D fig.2.
"Alarms" page
Access the "Alarm" page only if the machine detects one of the problems detailed below:
• Alarm: Supply air temperature <5°C
• Alarm: No Frost - Wait an hour
• Alarm : Ext Probe fault
• Alarm : Int Probe fault
• Alarm : Exh Probe fault
• Alarm: Sup Probe fault
Alarm with machine block: the messages "Alarm!" and "Block!" appear alternately on the "HOME" page.
Alarm without blocking the machine: on the "HOME" page, the message "Alarm!" Appears.
In the presence of alarms: select the "ALARM" line on the "MAIN MENU" page and press the [] key.
The dialogue window opens with the instructions on how to resolve the problem.
Warning:
!
After 2 minutes with no keys being pressed, the display returns to the "Home" page without saving any changes.
[ ▲ ]
occurs with machine block (manual reset).
occurs with machine block (manual reset).
occurs without blocking the machine (No Frost, Bypass: deactivated).
occurs without blocking the machine. ("By-pass": deactivated).
occurs without blocking the machine. (No Frost: deactivated).
occurs without blocking the machine.
MAIN MENU
USE MENU
ALARM
SETUP
INFO
035
VEXH1 = Stale air outlet to outside.
VEXH2 = Stale air outlet to outside.
VEXH3 = Stale air outlet to outside.
VEXHB = Stale air outlet to outside.
[ ▲ ]
[ ]
[ ▲ ]
57

Publicidad

loading

Este manual también es adecuado para:

Vort hri 200 flat iot hVort hri 350 flat iot