4. Operation
The condensed water flows into the neutralisation station sedimentation area. The integrated filter
plate is used to disperse the condensed water and have it flow through the granulate. The granulate
is then dissolved in the neutralised condensed water. The condensed water is then discharged the
pipework.
The quantity of neutralisation granulate in the delivery corresponds to the first fill at maximum
operation.
The pH of the condensed water circulated through the system is checked using pH indicator strips
which form part of the supply. The neutralization granulate should be recharged before the pH
reaches 6.5.
5. Content of supply
Basic equipment:
Accessories:
Consumables:
6. Technical characteristics
Connection characteristics
Nominal width of inlet/outlet pipe
Connection to discharge pipework, min.
Power data
Fuel/process (Gas/condensing technology)
Maximum neutralisation performance
corresponds to 0.14 l/kWh of maximum performance
of boiler
______________________________________________________________________________________________________________________________________________________________________
GB
 1 neutralisation station (Neutra N-70 or N-210) as a compact station
 1 manual
 1 plastic bag containing:
- 1 pack of pH indicator strips
- 3 pipe clamps
- 1 connecting sleeve for  20 pipe (for N-70 model)
- 1 connecting sleeve for  25 pipe (for N-210 model)
- 1 part for connection with vent tube for  40 siphon
- 1 adjustment part for  48 siphon
 5 m pipe DN 20 (for N-70 model)
 5 m pipe DN 25 (for N-210 model)
 Neutralisation granulate, Neutralit Hz
8 kg for N-70 model
3 x 8 kg for N-210 model
Waste water pumping system AH-300
Neutralit Hz - 25 kg
pH indicator strips - 3 pieces
-
- 20
Neutralisation Station
Neutra-N70 ; -N210
Neutra
N-70
[DN]
20
[DN]
40
Gas/Condensation
technique
[l/h]
70
[kW]
500
00ANO0001-#
N-210
25
210
1500

Publicidad

loading

Este manual también es adecuado para:

Neutra n-210