User Manual
6.8
Modbus setup menu (Modbus versions only)
Modbus Address :
4-20mA
PULSE
Modbus Baud :
4-20mA
PULSE
Modbus Comms :
4-20mA
PULSE
6.9
Pulse output menu
All models allow the use of a pulse output based on Volume pulse, Alarm, Energy pulse (Heat Meter versions only) or Frequency
indicating flow rate.
Select Pulse :
4-20mA
PULSE
Pulse Type :
4-20mA
PULSE
001
1200
8-None-2
OFF | ON
Volume
► Enter the Modbus Address for this unit. The valid range is 1 to
126.
► Press
to confirm the setting.
► Enter the baud rate for the Modbus network. Valid settings are
1200, 2400, 4800, 9600, 19200, or 38400.
► Press
to confirm.
► Select the Modbus data format. Valid settings are 8-None-2,
8-Even-1, 8-Odd-1, 8-None-1. The settings relate to the num-
ber of data bits in each character (8), the parity (Odd, Even or
none), and the number of stop bits (1 or 2).
► Press
to confirm.
► Press
to return to the Main Menu.
► Enable or disable the Pulse output using
ON.
► Press
to confirm the setting.
► Choose the Pulse type: Volume, Flow Alarm, Energy (HM
versions only), or Frequency.
► Press
to confirm.