User Manual
Diagnostics
4-20mA
Error :
PULSE
RTD Connected
4-20mA
PULSE
TOFM Connected
4-20mA
5060.01.01.01.03
PULSE
20.00.16.02.01
4-20mA
S/N : 0000000012345
PULSE
Gain40dB
4-20mA
DT
PULSE
None
01.01.01.00
SNR28dB
0.000 ns
This screen will display the Errors. A number between 0-255 will
be displayed. If no errors reported "None" is displayed.
The RTD board's firmware version is shown on the lower line. The
upper line shows its status.
The flow board's firmware version is shown on the lower line. The
upper line shows its status.
The unit's firmware version is shown on the upper line. The lower
line shows the unit's serial number.
Gain – a decibel number between -5dB and 80dB – lower is better,
should be around 40dB or below. Above 60dB need to question the
installation.
SNR (Signal/Noise ratio) in dB, scale is 0 to 80dB – higher is better.
Below 20, question the installation.
The lower line shows the current time differential between the
upstream and downstream signals.
Password-protected menus