5.14 Programming menu
5.14.1 General notes
The programming menu can be accessed via the integrated reset
button, or by remote reset during OPERATION and in STAND-
BY.
If in page menu the reset or remote reset button is not pressed
within 10 seconds the page will be automatically be exited and
there will be a green led blinking for the time set.
5.14.2 Block diagram for entering the menu
BURNER STATE
TEST OF
TYPE OF
SWITCHING OFF
FUNCTION
TIME OF
5 SEC.
RELEASE
BUTTON
NUMBER
2 RED
OUTPUT
BLINKS
OUTPUT
AUTOMATIC
S9653
Button
Function
release time
Test of
5s ≤ t < 10s
Switching off
Post-purging/
10s ≤ t < 15s
Continuous
purging
Intermittent
20s ≤ t < 25s
operation
Pre-purging
30s ≤ t < 35s
long
Display
35s ≤ t < 40s
lockout log
Parameter
40s ≤ t < 45s
reset
programming
menu
Installation
OPERATION (WITH FLAME) AND STAND-BY
POST-PURGING/
INTERMITTENT
CONTINUOUS
OPERATION
PURGING
10 SEC.
20 SEC.
1 GREEN
3 GREEN
10 SEC. AFTER
10 SEC. AFTER
RELEASE
RELEASE
No. of blinks of
No. of pressing times
the LED for
of the reset button
menu page
2 blinks
/ none
RED
1 GREEN blink
1 = 1 minute
2 = 2 minutes
3 = 3 minutes
4 = 4 minutes
5 = 5 minutes
6 = 6 minutes
7 = continuous purging
8 = 0 m (deactivated)
(default)
3 blinks
1 = 1 hour
GREEN
2 = 24 hours (default)
5 blinks
1 = activated
GREEN
2 = deactivated
(default)
6 blinks
1 = last lockout
GREEN
2 = 9th lockout
3 = 8th lockout
4 = 7th lockout
5 = 6th lockout
6 = 5th lockout
7 = 4th lockout
8 = 3rd lockout
9 = 2nd lockout
10 = less recent lockout
7 blinks
1 = reset of the lockout log
GREEN
2 = reset of the no. of
lockouts
3 = reset of hours of
operation
4 = reset of the no. of heat
requests
5 = restoration of default
values of the menu
parameters
If the number of presses on the reset or remote reset button ex-
ceeds the maximum allowable, the value that stays in memory
will be the maximum one.
If the reset or remote reset button is pressed for more than 60
seconds, a button error will be displayed and the control box will
restart.
LONG PRE-PURG-
DISPLAYING
ING
LOCKOUT
30 SEC.
35 SEC.
5 GREEN
6 GREEN
10 SEC. AFTER
10 SEC. AFTER
RELEASE
RELEASE
No. of blinks of
the LED (green)
/ none
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
1 blink
2 blinks
1 blink
2 blinks
Displaying the
type of lockout
according to
Tab. O
/
31
GB
PROGRAMMING
MENU PARAME-
LOG
TER RESET
40 SEC.
7 GREEN
10 SEC. AFTER
RELEASE
Quitting the menu
Automatic starting
from the end of the blink
10 sec. after the release of the
button
10 sec. after the release of the
button
10 sec. after the release of the
button
10 sec after the release of the
button (if at level 1).
When at level 2, 10 sec after the
display of the type of lockout or
else pressing the button again
before 10 sec you return to level
1 from where, 10 seconds after
nothing has been done to the
buttons, you exit the menu
10 sec. after the release of the
button
Fig. 24
Tab. R
20140262