General information
Burner description
Burner description
NC4, NC6 and NC9 fuel oil burners are
forced-draught burners, which operate
with an all or nothing firing rate.
These burners can be adapted to
different types of boiler. They are
available with an adjustable head
length. Details of the recommended
burner for any given boiler are available
on request. They use domestic fuel oil
with a density of 0.84 at a temperature of
10°C and with a heating capacity (Hi) of
11.86 kWh/kg.
These burners conform to the IP 21
protection level.
daPa
12
10
8
6
4
2
0
18
15
Burner
NC 4 R101A
NC 4 H101A
NC 6 R101A
NC 6 H101A
NC 9 H101A
Downloaded from
www.Manualslib.com
Packaging
The burner with its cover is supplied in a
package weighing about 10 kg which
contains:
- the assembly accessories kit,
- the document folder containing:
Space requirements and dimensions
Ensure there is a gap of at least 0.60 m
each side of the burner to allow for
maintenance operations.
NC4 R101A
mbar
daPa
1,2
1
0,8
0,6
0,4
0,2
0
40
25
35
45
Cell
Conical
flow
turbulator
kg/h
Ø 63/16-4
1.5 - 3.4
slots
Ø 63/16-4
1.7 -3.4
slots
MZ 770S
Ø 63/16-6
3.4 - 4.6
lg. 44 mm
slots
Ø 63/16-6
3.4 - 4.6
slots
Ø 75/20-6
3.8 - 8
slots
manuals search engine
- the operating instructions,
- the wiring diagram,
- the guarantee certificate.
NC4 H101A, NC6 H/R101A
12
10
8
6
4
2
0
40
20
15
25
35
45
55
Flame
Nozzle
Preheated
power
nozzle
kW
US gal/h
18 - 40
0.5 to 0.85
FPHB5
20 - 40
0.5 to 0.85
40 - 55
1 to 1.2
FPHB5
40 - 55
1 to 1.2
45 - 95
1.25 to 1.75
12/2008 - Art. Nr. 4200 1013 9300A
Boiler room ventilation
The required volume of new air is 1.2m
kWh produced by the burner.
Operating specifications
Ambient temperature:
- during use: - 5 - 40°C
- during storage: - 20 - 70°C
Max. electrical power consumed: 244W
(230V - 50Hz)
NC4
A
Min
270
Max
310
B
Min
70
Max
120
C
Ø
80
D
Min
21
Max
71
NC9 H101A
daPa
mbar
12
1,2
10
1
8
0,8
0,6
6
0,4
4
0,2
2
0
0
45
65
kW
40
50
60
70
Main components
• Safety unit: TCH1xx
• Pump and fan motor:
line
single-phase 230V, 50Hz, 2800 min
85-110W, 4µF/400V capacitor
• Electronic igniter:
EBI 5
no
• Blower turbine:
NC4/6: Ø133x42;
NC9: Ø133x62
• Air flap control: manual
• Fuel oil pump with solenoid valve:
no
AS47D
• Blast tube:
NC4/6: Ø63/80x177
no
NC9: Ø75/90x192
3
/
NC6
NC9
270
297
310
357
70
70
120
138
80
90
21
15
71
83
mbar
1,2
1
0,8
0,6
0,4
0,2
0
95
kW
80
90
100
-1
31