Commissioning
Commissioning the burner also involves
simultaneous installation by the fitter or
his representative; only they can
guarantee the boiler room complies with
currently accepted practices and
regulations in force.
Beforehand, the fitter must have
completely filled the suction line with fuel
oil, vented the primary filter and checked
that the manual quarter-turn and
protection valves function correctly.
Preliminary checks
• Check the available electric voltage
and compare it with the recommended
value.
Burner
NC4 R101A
NC4 H101A
NC6 H/R101A
NC9 H101A
Downloaded from
www.Manualslib.com
• Switch off the burner power supply.
• Check absence of voltage.
• Close the fuel valve.
• Read the manufacturer's service
• Check the following:
Nozzle Danfoss S
Boiler pow er
Fuel-oil flow
US Gal/h
kW
kg/h
Spray angle
45°
20
1,8
-
24
2,2
-
27,3
2,5
-
32,7
3,0
0,75
37,1
3,4
0,85
43,6
4,0
1,00
48
4,4
1,10
54
4,9
1,25
67
6,1
1,50
74
6,8
1,75
1
2
3
4
5
6
7
10
Y1
Check for fuel oil leaks
• Connect a pressure gauge and a
• The readings are taken while the
• Check subsequently for leaks.
manuals search engine
instructions for the boiler and the
regulator.
- the water pressure in the heating
circuit,
- the operation of the circulator,
- the opening of the mixer valve,
- the setting of the boiler thermostat
and the ambient thermostat,
- the rating of the fuses,
- that the combustion air supply to the
boiler house and the combustion
Pump
Dimension
Air flap
pressure
Y
103B
bar
mm
Scale values
60°
0,50
11
5
0,60
11
5
0,60
11
10
-
11
10
-
11
10
-
11
12
-
11
20
-
11
5
-
11
10
-
11
15
Suction.
Return.
Nozzle outlet.
Pressure tap
Vacuum gauge connector
Pressure setting.
Single line indication.
Solenoid valve coil.
Solenoid valve.
vacuum gauge to the pump.
burner is operating.
12/2008 - Art. Nr. 4200 1013 9300A
product exhaust pipe are working
correctly and compatible with burner
capacity and fuel,
- the operation of the draught
regulator on the flues,
- the fuel oil level in the tank,
- that the aspiration line has been
filled,
- the position of the hoses:
- suction and return,
- the supply pressure of the fuel, if
boost: 2 bar max,
- the opening of the protection and
primary filter valves.
Setting
The burner is preset in the factory.
If this pre-setting does not correspond to
the boiler power, follow the instructions
below.
9
• In the table opposite, choose the
nozzle calculated for the nominal
10
power of the boiler with an efficiency
10
rating of 92%.
13
• Carry out the following settings on the
15
combustion head:
15
- dimension Y graduated from 0 to
18
20 mm,
- manual control of the air flap
8
103B graduated from 0 to 18.
11
Firing
13
• Close the regulator circuit.
• Unlock the control unit.
• The burner is in service.
• Wait until the reheater thermostat has
closed (for burners with reheaters).
The burner starts up
• Carry out a combustion check: CO
opacity and exhaust gas temperature.
To increase the CO
2:
• Reduce the air flap opening and vice
versa. Modifying its value may require
a correction of dimension Y, by turning
screw 3.
To modify the exhaust gas index
• Open the air flap to make it lighter, and
vice versa.
• Check the combustion parameters
under actual operating conditions
(doors closed, etc.), and test that the
various circuits are sealed.
• Record the results in the relevant
documents.
Safety checks
• Check, while the burner is functioning:
G1/8
- the opening of the regulator circuit,
G1/8
- the safety shutdown with lockout,
with no flame,
- the seal on the boiler front,
- the operation of the control devices
(if present),
- the vacuum pressure of the fuel
supply circuit, maximum 400 mbar
or 305 mm Hg.
,
2
33