Descargar Imprimir esta página

Baxi Luna Duo-Tec MP+ 1.110 Manual De Uso Destinado Al Usuario Y Al Instalador página 36

Ocultar thumbs Ver también para Luna Duo-Tec MP+ 1.110:

Publicidad

Idiomas disponibles

Idiomas disponibles

Use the Remote Control to set the programmable timer for heating and DHW. See the instructions supplied with the accessory.
SETTING PARAMETERS USING THE REMOTE CONTROL
Turn knob B
Press knob B
Press button A or C
KEY TO FIGURE MENU
1
Enduser
2
Commissioning
ALL MODIFIED PARAMETERS SHOULD BE NOTED
DOWN IN THE TABLE AT THE END OF THIS MANUAL.
The following procedure is used to access the four boiler
programming menus:
• from the main menu
A and C (hold down for approx. 6 seconds)
B
menu 1-2-3-4 (see figure to side and key).
C to go back one menu at a time to the main menu.
When the Control Panel is wall-mounted enable the room
sensor and flow temperature modulation as follows:
A) ROOM SENSOR
• Access menu 2.
B
Operator unit
B
programme row 40 (Used as)
B (anti-clockwise)
C to return to the previous menu then
B
programme row 5977 (Function input H5) then
B
None
B to confirm.
For correct operation of the environment unit during the reduced time band it is necessary to set the parameter 5977 = "none".
B) FLOW TEMPERATURE MODULATION
To set flow temperature modulation, disable parameter 742 (HC1). Proceed as follows:
• Access menu 2.
B
Temps / mode CH1
B (anti-clockwise)
If, when turning the knob B on the main menu, the display visualises the boiler flow temperature instead of the ambient
temperature, parameter 742 has not been set correctly.
After every system configuration (e.g.: solar combination, connection an external storage boiler, etc.) perform the following
procedure to update the boiler board to the new configuration:
• Access menu 2 as indicated at the beginning of this section.
B
Configuration
B
Yes then
B to confirm.
ZONE SYSTEM WITH INSTALLATION OF THE REMOTE CONTROL
The electrical connection and the adjustments required to manage a system divided into zones with use of the Remote Control
differs according on the accessories connected to the boiler. To install and configure, see the instructions of the Expansion
Module supplied as an accessory.
ADJUSTING THE TEMPERATURE OF THE HIGH TEMPERATURE HEATING SYSTEM
To avoid frequent starting and stopping, raise the minimum temperature setpoint of the boiler in the heating mode by setting
parameters 740, to not less than 45°C, using the procedure described in point B.
7221409.03 (2-07/16)
SYMBOLS FOR REMOTE CONTROL
3
Engineer
4
OEM
C.
B to confirm.
B.
Room unit 1
B to confirm (the room sensor is now active).
B
B to confirm
"---" then
B to confirm.
B
B
programme row 6200 then
Display shows
Press button A and knob B together
Press buttons A and C together
Configuration
B.
B to confirm.
B
742 (Flow temp setpoint room stat)
B.
36
B to confirm.

Publicidad

loading

Este manual también es adecuado para:

Luna duo-tec mp+ 1.90