BMP 01- EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System
7
IO-Link interface (continued)
7.5.2
Switching signal configuration (SSC)
Before starting the switching signal
configuration, the measurement value configu-
ration (see sec. 7.5.1) must be completed!
The BMP has 4 integrated switching signals. Each
switching signal is described by two parameters
(Parameter and Configuration). The BMP has implemented
the switching signals in accordance with the smart sensor
profile as Window mode.
Hysteresis
SSC
OFF
ON
SP1
Fig. 7-2:
SSC hysteresis
Parameter
Subindex
SSC Parameter
SSC1: 0x003C (60)
SSC2: 0x003E (62)
SSC3: 0x4000 (16384)
SSC4: 0x4002 (16386)
SSC Configuration
SSC1: 0x003D (61)
SSC2: 0x003F (63)
SSC3: 0x4001 (16385)
SSC4: 0x4003 (16387)
Tab. 7-8:
SSC parameter data
– As the factory default, SSC 1 has an
In-Range switch point (see section 6.3 on
page 15)
– SSC 1 is placed on output Out 1 in SIO
mode.
The BMP supports the Single-Teach functions in
accordance with the smart sensor profile. Two additional
parameters are used for this teach-in process (TI Select
and TI Result; see Tab. 7-9).
Index
Subindex
TI Select
0x003A (58)
TI Result
0x003B (59)
Tab. 7-9:
Teach In parameter data
www.balluff.com
Hysteresis
OFF
Measurement value
SP2
Name
1
Setpoint 1 (SP1)
2
Setpoint 2 (SP2)
1
Logic
2
Mode
3
Hysteresis
Size
Access
0
1 byte
Read/Write 0 or 1 = SSC1 (default)
0
1 byte
Read Only
Size
Access
Values
4 bytes
Read/Write 32-bit integer value [µm]
4 bytes
Read/Write 32-bit integer value [µm]
0 = Normally open (NO, default)
1 byte
Read/Write
1 = Normally closed (NC)
0 = Deactivated
1 byte
Read/Write
2 = Window mode (default)
2 bytes
Read/Write 100 to 30000 μm (default: 100 µm)
The distance between SP1 and SP2 must be at
least 2x the hysteresis in order for the switch-
point to function.
Values
2 = SSC2
3 = SSC3
4 = SSC4
0x00 (0) = inactive
0x11 (17) = Teach In of SP1 successful
0x42 (66) = Teach In of SP2 successful
0x07 (7) = Error
english