N700E
MANUAL
DE
INSTRUCCIONES
Nombre
Simbolo
del
terminal
terminal
Frequency
H
command
power terminal
Frequency
commanding
O
terminal(voltage
commanding)
Frequency
commanding
OI
terminal(current
command)
Frequency
command
L
common
terminal
Frequency
FM
monitor
FA1
(1)
Frequency
FA2
arrival signal
(2)
RUN
Run signal
(0)
Overload
OL
advance
(3)
notice signal
OD
PID control error
(4)
deviation signal
AL
Alarm signal
(5)
AL0
AL1
Alarm terminals
AL2
del
When assign 13[AT signal] to code C01~C06
•
AT signal OFF :
It is possible to command frequency using voltage signal terminal O-L(0~10V)
•
AT signal ON :
It is possible to command frequency using current signal terminal OI-L(4~20mA)
When not assign 13[AT signal] to code C01~C06 It is possible to commend frequency
use the algebraic sum of both the voltage and current input
• Frequency limit by frequency order method :
Voltage input order(DC 0~10V)
A61 : Minimum frequency(0Hz), A62:Maximum frequency(Enable to A04 Setting value)
Current input order(4~20mA)
A63 : Minimum frequency(0Hz), Maximum frequency(Enable to A04 Setting value)
Analog output frequency monitor/ analog output current monitor/ analog output
voltage monitor
Frequency arrival [FA1][FA2] signals is indicated
when the output frequency accelerates and
decelerates to arrive at a constant frequency.
When the [RUN] signal is selected, the inverter
outputs a signal on that terminal when it is in
the RUN mode.
When the output current exceeds a preset value,
the [OL] terminal signal turns on.
When the PID loop error magnitude the preset value,
the [OD] terminal signal turns on.
The inverter alarm signal is active when a fault
has occurred.
At normal status, power off(initial setting value)
At abnormal status
Contact rating : 250V AC 2.5A(resistor 1oad) 0.2A(inductor load)
Descripción
30V DC 3.0A(resistor 1oad) 0.7A(inductor load)
(minimum 100V AC 10mA, 5V DC 100mA)
5-2
Output terminal
specification
250VAC, 2.5A
(Resistive load)
30VDC, 3A
(Resistive load)
: Al0 - AL1(closed)
: AL0 - AL2(closed)