N700E INSTRUCTION MANUAL
Overload Advance Notice Signal [OL]
When the output current exceeds a preset value,
the [OL] terminal signal turns on.
The parameter C18 sets the overload threshold.
The overload detection circuit operates during powered
motor operation and during regenerative braking.
The output circuits use relay output,
and are active low.
Option
Terminal
Code
Symbol
3
OL
Valid for inputs:
Required setting
Notes:
• The default value is 100%.
To change the level from the default,
set C18 (overload level).
• The accuracy of this function is the same
as the function of the output current monitor on the
[FM] terminal
Function Name
Overload advance
notice signal
C13, C14, C18
3
Input
State
when output current is more than the set threshold
ON
for the overload signal.
when output current is less than the set threshold
OFF
for the overload signal.
5-18
Description