Alarm Terminal Function - Hyundai N700E Manual De Instrucciones

Tabla de contenido

Publicidad

N700E INSTRUCTION MANUAL
5.5

Alarm Terminal Function

Alarm Terminal [AL1, AL2-AL0]
The alarm output terminals are connected as shown below by default, or after initialization.
The relay contacts normally contact a.
Convention uses "normal' to mean the inverter has power and is in Run or Stop Mode.
The relay contacts switch to the opposite position when it is Trip Mode or when input power is off.
During normal running or power is turned off
AL0
AC250V, 2.5A(Resistor load), 0.2A(Inductive load)
DC30V, 3.0A(Resistor load), 0.7A(Inductive load)
Contact a (Initial setting)
AL1
AL2
Contact
Power
ON
Contact a
ON
(initial
Setting)
OFF
Contact specification
Maximum
When an alarm occurs
Run State
AL0-AL1
Normal
Open
Trip
Closed
-
Open
5-21
AL0
AL1
AL2
AL0-AL2
Closed
Open
Closed
Minimum
AC100V, 10mA
DC5V, 100mA

Publicidad

Tabla de contenido
loading

Tabla de contenido