Intelligent Input Terminal Function - Hyundai N700E Manual De Instrucciones

Tabla de contenido

Publicidad

N 00E
7
MANUAL
DE
INSTRUCCIONES
5.3

Intelligent Input Terminal Function

Forward Run/Stop [FW] and Reverse Run/Stop Command [RV]
• When you input the Run command via the terminal [FW], the inverter executes the
Forward Run command (high) or Stop command(low)
• When you input the Run command via the terminal [RV], the inverter executes the
Reverse Run command (high) or Stop command(low).
Option
Terminal
Code
Symbol
0
FW
1
RV
Valid for inputs:
Required setting
Notes:
• When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
• When a terminal associated with either [FW] or
[RV] function is configured for normally closed,
the motor starts rotation when that terminal is
disconnected or otherwise has no input voltage.
Set the parameter
DANGER : If the power is turned on and the Run command is already active, the motor starts
rotation and is dangerous! Before turning power on, confirm that Run command is not active.
Function Name
Forward Run/Stop
Reverse Run/Stop
C01,C02,C03,C04,
C05,C06
A02=01
A02 to
1
State
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Run Mode, motor stop
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Run Mode, motor runs stop
Example: