You have just obtained a resistance, capacity or inductance
decade box, and we thank you for your trust in us.
To obtain the best service from your unit:
read these operating instructions carefully,
comply with the precautions for use.
1
GENERAL INSTRUCTIONS
If the device is used in a manner unspecified in these
instructions, the protection provided by the device may be
compromised.
1.1
UNPACKING – PACKING
All instruments are checked mechanically and electronically
before shipment. All precautions are taken to be sure you
receive an undamaged instrument. If there is damage, notify the
carrier immediately.
1.2
PRECAUTIONS AND USAGE SAFETY
1.2.1
Before any use
Resistance, condenser and inductance decade boxes are
passive elements to be inserted into trial or development
circuits to obtain the desired resistance, capacity or inductance
values by a combination of decades.
These decade boxes are compliant with safety standard IEC
61010 – 1.
For your own safety and to prevent any damage to your
equipment, you must follow the instructions in this manual.
This equipment can be used in category II electrical circuits not
exceeding 150V relative to earth. It must be used indoors in an
environment with level 2 pollution and at an altitude below
2,000m.
Definition of Installation Categories (see IEC 61010-1)
CAT I: Circuits not directly connected to network and
specially protected.
Example: protected electronic circuits.
CAT
II:
Circuits
connected
installation.
Example: power supply for domestic electrical appliances
and portable tools.
CAT III: Power supply circuits in the building installation.
Example: Electrical panel, circuit breakers, fixed industrial
machines or devices.
CAT IV: Source circuits of building low-voltage installation.
Example: Power feeders, counters and protection systems.
BR04-05-06-07 – BC05 – BL07
directly
to
low-voltage
13