Grounding connection for battery:
M5x10 and
PH2x150mm
2.5N.m
6.3. AC Connection
6.3.1. Requirements for the AC Connection
DANGER
DANGER
AC cable requirements as follows:
Conductor type: copper wire
External diameter: 9mm to 18mm for grid connector, 10mm to 14mm for backup connector
Conductor cross-section area recommendation: 10mm² for grid connection, 6mm² for
backup connection
Insulation stripping length: 10mm
Sheath stripping length: 50mm
© 2023 Maxeon Solar Technologies, Ltd. All rights reserved. | 547143 Revision B - June 2023
Specifications included in this document are subject to change without notice
7.5-9.5mm
6-10mm²
Residual-current monitoring unit: The inverter does not require an
external residual-current device when operating. If local regulations
require the use of a residual-current device, or Hybrid-coupled storage
system with big coupling capacity from the PV array and PV inverter,
the following must be observed: The inverter is compatible with type A
residual-current devices with a rated residual current of 100 mA or higher.
Each inverter in the system must be connected to the utility grid via a
separate residual-current device.
Protection devices: You must protect each inverter with an individual
grid/backup circuit breaker to ensure that the inverter can be
disconnected safely.