SVT:1 Mode
Under this operation mode, the user does not define a specific voltage
test, but a maximum voltage value. The device will start the test applying
a 500 V voltage and increase this value in 500 V steps each minute until
reaching the programmed voltage. At each stage, the MD5060x
measures the resistance before advancing towards the following step.
The use of voltage adjusting keys, determines the value of the highest
voltage – which will be, in all cases, a multiple of 500 V, up to a 5000 V
limit. It is advisable to use the
key may be used, but if the selected value is not a multiple of 500, it will
be rounded down.
SVT:2 Mode
In this mode, if the maximum voltage value is set to 2500 V or lower, the
test will perform the same way as SVT:1 mode.
If the maximum voltage is set to a higher value than 2500 V, the test will
always perform 5 steps with one minute duration each. The step voltage
value will be the defined max. voltage divided by 5.
Example: if the max. voltage is set to 3000 V, the step voltage will be
600 V.
key in order to select this value;
10k
100k
1M
10M
100M
1G
10G
10k
100k
1M
10M
100M
1G
10G
19
100G
1T
100G
1T