5.2.2. SVT Mode (step voltage tests)
The use of
key allows the MD-5060x setting for the performance of a
step voltage test; when this mode is selected, the display shows the SVT
abbreviation.
Under this operation mode, the user does not define a specific voltage
test, but a maximum voltage value. The device will start tests applying a
500 V voltage and increase this value in 500 V steps each minute until
reaching the programmed voltage. At each stage, the MD-5060x
measures the resistance before advancing towards the following step.
The use of voltage adjusting keys, determines the value of the highest
voltage – which will be, in all cases, a multiple of 500 V, up to a 5000 V
limit. It is advisable to use the
key in order to select this value;
key may be used, but if the selected value is not a multiple of 500, it will
be rounded down.