* In the case all connected indoor unit models are Case 1 or Case 2, do NOT add the refrigerant listed in table Ⓐ. Instead, add the following
amount of refrigerant.
Case 1: TPLFYP006/018/036EM14**
→ Add 0.67 kg per TPLFYP006/018/036EM14**.
Case 2: TPEFYP006/024/036MA14**
→ Add 0.55 kg per TPEFYP006/024/036MA14**.
・When the piping length from the outdoor unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
High-pressure pipe ø28.58
additional charge
=
total length
(kg)
× 0.33 (kg/m)
Liquid pipe ø15.88 total
+
length
× 0.18 (kg/m)
Main or sub BC controller
+
Total capacity of
outdoor units
Single
+
Combination
* When connecting TPLFYP006EM14**, TPLFYP018EM14**, or TPLFYP036EM14**, add 0.67 kg of refrigerant per indoor unit.
* When connecting TPEFYP006MA14**, TPEFYP024MA14**, or TPEFYP036MA14**, add 0.55 kg of refrigerant per indoor unit.
<Example>
Outdoor unit 1 model: P120
Outdoor unit 2 model: P120
BC controller (Main) model: TCMBM0108JA11N4
BC controller (Sub) model: TCMBS0104KB11N4 × 4 units
Total capacity of connected indoor units: 206
* Refer to the pipe connection examples in section 9-4 for the pipes marked with the letters below.
A:
ø28.58; 40 m
B:
ø9.52; 10 m
C:
ø9.52; 5 m
D:
ø9.52; 5 m
E:
ø9.52; 5 m
F:
ø9.52; 5 m
G: ø9.52; 5 m
H:
ø9.52; 5 m
I:
ø9.52; 5 m
A
: ø19.05; 3 m
1
A
: ø19.05; 1 m
2
a:
ø9.52; 10 m
b:
ø9.52; 5 m
c:
ø6.35; 5 m
d:
ø6.35; 10 m
e:
ø6.35; 5 m
f:
ø9.52; 5 m
WT09115X03
High-pressure pipe ø22.2
+
total length
× 0.21 (kg/m)
Liquid pipe ø12.7 total
+
length
× 0.11 (kg/m)
Amount (kg/unit)
J-type
1.5
JA-type
3.0
KA-type
4.7
KB-type
0.4
Amount (kg)
(to be added for outdoor unit)
72
0
96
0
120
0
144
0
168
0
192
4.4
216
4.4
240
4.4
192
0
216
0
240
0
264
0
288
0
312
0
336
0
384
8.8
432
8.8
High-pressure pipe ø19.05
High-pressure pipe ø15.88
+
total length
+
total length
× 0.14 (kg/m)
× 0.1 (kg/m)
Liquid pipe ø9.52 total
Liquid pipe ø6.35 total
+
length
+
length
× 0.054 (kg/m)
× 0.021 (kg/m)
Total capacity of connected
indoor units
(to be added for indoor unit)
27 or below
28 to 54
55 to 126
127 to 144
145 to 180
+
181 to 234
235 to 273
274 to 307
308 to 342
343 to 411
412 to 450
451 or above
GB-29
Amount (kg)
2.0
2.5
3.0
3.5
4.5
5.0
6.0
8.0
9.0
10.0
12.0
14.0