8.2
Capacity of the generating set
Before connecting and operating the unit, calculate the electrical power required by the units to be used (in watts)*. To ensure
optimal operation, the total wattage of all equipment used at the same time must be:
-
greater than 60% of the rated load for the unit (risk of insufficient load);
-
less than the rated load for the unit during continuous operation (risk of overload).
If the unit is run under or over its rated load frequently or for long periods of time, it can start to wear very quickly. Damage caused
in this way will not be covered by the warranty.
*This load is usually indicated in the technical specifications or on the manufacturer's plate for the equipment. Some equipment requires a higher
load when starting. This minimum required power must not exceed the unit's maximum power.
8.3
Generating set identification
The generating set identification plate is affixed to the outside of the enclosure.
(C)
(D)
(B)
(E)
Serial numbers will be required when requesting troubleshooting advice or spare parts.
To keep them safe, note down the serial number of the generating set below.
Generating set serial number:......../.............. - ........................ - .........
8.4
Specifications
Model
Maximum power
Rated power
Acoustic pressure at 1 m
Acoustic measurement uncertainty
Engine type
Maintenance kit
Fuel tank capacity
Recommended fuel
Recommended oil
Oil sump capacity
Oil cut-out*
Direct current
Alternating current
Circuit breaker(s)**
Socket type
Type of spark plug
Battery
Dimensions l x w x h
Weight (without fuel)
o: standard
*Oil cut-out: If there is no oil in the engine sump or if the oil pressure is low, the oil cut-out mechanism automatically stops the engine to prevent any
damage. If this occurs, check the engine oil level and top it up if necessary before looking for any other cause of the problem.
**Circuit breaker: The generating set's electrical circuit is protected by one or more magnetothermal, differential or thermal cut-out switches. In the
event of an overload and/or short circuit, the supply of electrical energy may be cut. If necessary, replace the circuit breakers in the generating set
with circuit breakers with identical nominal ratings and specifications.
(A)
(F)
(L)
(M)
INVERTER PRO 3000 E
2 x 2P+T 230V 10/16A / 1 x 12V 12A
(G)
(I)
(G)
(H)
(J)
(K)
3000 W
2800 W
73 dB(A)
0,7 dB(A)
YAMAHA MZ175
RYS3
13 L
Unleaded petrol
SAE 10W30
0,6 L
o
12V - 12A
230V - 12,2A
o
BPR4ES
o
68 x 44,5 x 55,5 cm
68 kg
x: not applicable
Example of an identification plate
(A): Model
(B): CE marking
(C): Maximum
(D): Nominal power
power
(E): Power factor
(F): Earth
(G): Current
(H): Current
amperage
frequency
(I):
Current
(J):
voltage
index
(K): Reference
(L):
standard
(M):
Guaranteed acoustic power level
INVERTER PRO 3000 E PrIndus
3000 W
2800 W
73 dB(A)
0,7 dB(A)
YAMAHA MZ175
RYS3
13 L
Unleaded petrol
SAE 10W30
0,6 L
o
12V - 12A
230V - 12,2A
o
2 x 2P+T 230V 16A / 1 x 12V 12A
BPR4ES
o
68 x 44,5 x 55,5 cm
68 kg
Protection
Serial number