5.14.8 Displaying the lockout log
The control box allows you to display the last 10 lockouts that oc-
curred and were logged, accessing the Programming menu on
page 31.
Access to this page is possible both in STAND-BY, as well as in
the OPERATING status.
Display sequence of the last lockout that occurred
 Keep the button pressed for 35 sec. = t < 40 sec.
 The GREEN led blinks 6 times.
 Release the button.
 Displaying the type of lockout memorised for 10 sec.
The time displaying the type of lockout can be extended by re-
pressing the reset button during the display of the lockout (the
lockout display continues for another 10s).
NOTE:
(*) Always wait 1 sec. with each pressing and release of the
button to ensure the command is logged correctly.
5.14.9
Resetting the programming menu parameters
and the lockout log
The control box allows you to reset the log and the number of
lockouts, the operating hours, the number of ignitions and recov-
er the menu's default, see paragraph "Block diagram for enter-
ing the menu" on page 31.
Sequence for setting and restoring the parameters
 Programming allowed in OPERATING mode and in STAND-
BY.
 Press the button for 40 sec. ≤ t < 45 sec.
 The GREEN led blinks 7 times.
 Release the button.
 GREEN led OFF
 Press the button 1 time to reset the lockout log (*)
 Press the button 2 times to reset the number of lockouts (*)
 Press the button 3 times to reset the number of hours oper-
ating with flame (*)
 Press the button 4 times to reset the number of heat
requests (*)
 Press the button 5 times to reset all the default values of the
parameters of the PROGRAMMING MENU (*)
 GREEN led ON and OFF every time press and release
 After 10 sec., the GREEN LED will blink for the number of
times programmed (0.5 sec. ON; 0.5 sec. OFF).
Installation
33
GB
20135737