I.6
MENU NAVIGATION
Livello 0 (Display)
Visualizzazione
temperatura sonda o
allarme
I.6.1
LED STATUS SIGNALS
○ COMPRESSOR STATUS LED
• Off: compressor stopped.
• On: compressor running.
• Flashing: time delay.
○ DEFROST STATUS LED
• Off: defrosting is not active.
• On: defrosting is active.
• Flashing: time delay.
○ PLATE HEAT-EXCHANGER ELECTRIC HEATER LED
• Off: heater element off.
• On: heater element on.
Alarm
E01
High pressure
E02
Low pressure
E04
Fan/compressor thermal protection
E05
Anti-freeze protection
E06
Water side heat exchanger outlet water sensor faulty
E07
Temperature/pressure sensor faulty
E40
Water side heat exchanger inlet water sensor faulty
E41
Differential pressure switch
I.6.3
LIST OF OPERATING STATUSES
This allows the user to view and monitor the operating status of all the
devices fitted to the unit, in real time.
To view, press the MODE-UP and ON/OFF, RESET-DOWN keys
simultaneously the label SET will be displayed.
Use the UP/DOWN keys to view all the sub-labels and decode them. To
return to the opening menu, just press MODE-UP and ON/OFF,RESET-
DOWN 3 times, for 2 seconds.
Livello 1
Label Set cooling: Coo
Set point: SET
Label Set heating: HEA
Valore sonde: tP
Allarmi: Err
Code allarmi attivi: E xx
Parametri: Par
Param. configurazione: CnF
Param. compressore.: CP
Param. ventilazione: Fan
Param. pompa: PUP
Param. antigelo: Fro
Param. sbrinamento:dFr
Password: PSS
Ore compressore: OH 1÷OH 2
Ore funzionamento:
OHR
Parametri accessibili con Password.
Alarm description
Livello 2
Code ing.: t 01-t 03
Param. allarmi: ALL
Valore Password
Ore pompa: OHP
I.6.2
ALARM SIGNALS
IMPORTANT!
Malfunctions and alarms displayed by the machine
should NEVER be ignored. The problem should be
checked and resolved as soon as possible.
If the alarm re-occurs, call technical assistance.
An alarm condition is indicated by the display on the panel of the
corresponding alarm code, as per the table below.
○ In the case of an alarm with manual reset:
• check with the help of the table, which alarm is indicated;
• reset the alarm using the ON/OFF RESET key;
• check that the unit starts up again correctly.
MANUAL
AUTOMATIC 3 times, then MANUAL
MANUAL
MANUAL
AUTOMATIC
AUTOMATIC
AUTOMATIC
AUTOMATIC 3 times, then MANUAL
Label
Sub-label
Ohr
(password
required)
Error
TP
24
Livello 3
Valore set cooling
Valore set heating
Valore Sonde
Indice par.: H 27 e H49
Valore parametro
Parametri: C 03 e C 04
Valore parametro
Parametri: F25
Valore parametro
Param.: A 04,A 06,A 11
Valore parametro
Parametri: r 07, r 08
Valore parametro
Parametri: d 02÷d 09
Valore parametro
Numero ore
Numero ore
Reset
Display (Meaning)
Number of compressor operating hours
OH1
since last hours reset
Number of pump operating hours since
OHP
last hours reset
List of active alarms
T01
Temperature in °C of inlet water sensor
T02
Temperature in °C of outlet water sensor
Temperature/pressure in °C/bar of the
T03
external heat exchanger sensor