BTL BNC_ 00- _ _ _ _ -B15A _010-000S92 / BTL ZNC_ 00- _ _ _ _ -B15A _010-000S92
Magnetostrictive Linear Position Sensor – Rod Style
Installation
For examples and further information on
installation, see the user's guide.
Suitable nuts for the mounting thread are
available as accessories.
We recommend using non-magnetizable material to mount
the BTL and magnet.
If using magnetizable material, the BTL must be protected
against magnetic interference through suitable measures
(e.g. spacer ring made of non-magnetizable material, a
suitable distance from strong external magnetic fields).
If installed in a hydraulic cylinder, the magnet should not
make contact with the rod. Minimum bore diameter in the
support piston:
Rod diameter
10.2 mm
NOTICE
Interference in function
Improper installation can compromise the function of the
BTL and result in increased wear.
► Ensure that the contact surface of the BTL is in full
contact with the mounting surface.
► Seal the hole perfectly (O-ring/flat seal).
Mounting in a hole with internal thread (mounting
hole)
Depending on the version, the BTL comes with an
M18×1.5 thread (according to ISO) or a 3/4"-16UNF
thread (according to SAE) to secure it.
1. Make a mounting hole with thread (possibly with
countersink for the O-ring.
2. Screw the BTL with mounting thread into the mounting
hole (max. torque 75 Nm).
Mounting in a through-hole
Mounting in a through-hole is only permitted
under ambient atmospheric pressure.
1. Guide the BTL through the hole.
2. Screw the mounting nut (max. torque 75 Nm) onto the
mounting thread on the rod side.
Further steps Further steps
► Install the magnet (accessory).
► From 500 mm measuring length: Support the rod and,
if necessary, screw it on at the end (with threaded rod
end).
www.balluff.com
Bore diameter D2
At least 13 mm
Shielding and cable routing
Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
Observe the following instructions to ensure
electromagnetic compatibility (EMC):
Connect BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Shield is internally connected to connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL and the transducer/holding cylinder and strong,
external magnetic fields.
Cable routing
All cables between BTL, control and power supply must
be routed tension-free. In order to avoid electromagnetic
interference, ensure sufficient distance to cables carrying a
heavy current and cables with high-frequency voltage
signals (e.g. of frequency converters).
Only approved cables with a minimum size of
AWG 24 may be used. All connected cables
must have a temperature resistance of at least
85 °C. Use copper conductor, only.
Cable length
BTL ...-B15AA/A1...
BTL ...-B15AE/A5...
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
Electrical connection
The electrical connection is made via a plug connection.
See the information about Shielding and cable
routing.
2
5
1
3
Pin assignment of S92 (view from
4
above on BTL)
Pin ...-B15AA... ...-B15A1... ...-B15AE... ...-B15A5...
1
10...30 V
2
0...10 V
10...0 V
3
4
Unassigned
5
1) Reference potential for supply voltage and EMC-GND.
2) Unassigned leads that are not used can be connected to the GND on
the controller side but not to the shield.
Max. 30 m
1)
Max. 100 m
1)
4...20 mA
20...4 mA
GND
1)
2)
0 V
english